Sauter flexotron®800
ventilation
Installation and wiring
P100012082
26
3.8
Wiring diagram RDT808
(Configuration 808 fixed-value)
(See also: Figure for terminal assignment, page 14)
LS
Power supply 24 V AC ±15%. 50/60 Hz
or 24 V DC
1
D+
RS485 Modbus (not with
web (TCP/IP) models)
MM
2
D-
Earth conductor
3
C
+24 V +24 V DC. Reference point for digital inputs DI
4
E
42
LS
Reference point for digital outputs DO
-
-
-
41
DO1
Heating coil pump
-
-
40
DO2
Supply air fan, level 2
-
-
34
Reference potential for analogue inputs AI
9
DI1
External OFF switch
33
AI1
Outside-temperature sensor
10
DI2
Frost-protection facility
32
AI2
Sensor for supply air temperature
11
DI3
Supply air fan on
17
Reference potential for analogue
outputs AO
18
AO1
Actuator for heater Y1