BA_EQJW126F001_EN001
29
Functions of the heating circuit
Parameters
WE
Parameter level /
Range
of
values
Flow
Point 1
70.0 °C
PA1
/ 5.0 to 130.0 °C
temperature
Point 2
55.0 °C
Point 3
40.0 °C
Point 4
25.0 °C
Reduced flow Point 1
60.0 °C
PA1
/ 5.0 to 130.0 °C
temperature
Point 2
40.0 °C
Point 3
20.0 °C
Point 4
20.0 °C
Return flow
Points 1 to
65.0 °C
PA1
/ 5.0 to 90.0 °C
temperature
4
Min. flow temperature
20.0 °C
PA1
/ 5.0 to 130.0 °C
Max. flow temperature
90.0 °C*
PA1
/ 5.0 to 130.0 °C
* With CO1 -> F05 - 1, the following applies: Max. flow temperature / 5 to 50 °C (50 °C)
5.2
Fixed set point control
During the times-of-use, the flow temperature can be controlled according to a
fixed set point. Outside the times-of-use, the controller regulates to a reduced flow
temperature.
Set the desired rated flow temperature as
Day set point
, and the reduced flow
tempera- ture as
Night set point
.
Functions
WE
Configuration
Outdoor sensor AF
1
CO1 -> F02 - 0
Parameters
WE
Switch position / Range of values
Day set point
Night set point
50.0 °C
30.0 °C
/ Min. to max. flow
temperature
/ Min. to max. flow temperature
Parameters
WE
Parameter level / Range of values
Min. flow temperature
Max. flow temperature
20.0 °C
90.0 °C
PA1 / 5.0 to 130.0 °C
PA1 / 5.0 to 130.0 °C
5.3
Underfloor heating/drying of jointless floors
Using function block setting CO1 -> F05 - 1, the respective heating circuit is
configured as an underfloor heating circuit. In doing so, the controller at first only
Содержание equitherm EQJW126F001
Страница 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Страница 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Страница 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Страница 28: ......
Страница 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Страница 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Страница 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Страница 49: ......
Страница 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Страница 58: ......
Страница 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Страница 63: ......
Страница 65: ...Communication BA_EQJW126F001_EN001 51 Station address ST 255 PA6 1 to 247 with CO6 F02 1 1 to 32000 ...
Страница 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Страница 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Страница 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Страница 80: ......
Страница 82: ...Fig 7 Connecting the EQJW126 Controller with standard back panel Electrical connection 62 BA_EQJW126F001_EN001 ...
Страница 89: ...Appendix BA_EQJW126F001_EN001 69 F Function block number WE Default value Anl System code number ...
Страница 92: ......