EQJW145: Heating controller
Using the controller
88
7010015003 A
© Fr. Sauter AG
8.2.3
Control model 3
PI
2P
SP 49
Fig. 11: EQJW 145 control model 3
Weather-compensating flow temperature control (secondary) and separate
fixed value control (secondary) for DHW preparation in converter installations
Main SERVice parameters (see also 3.3):
SP06
2
(Control model)
SP07
1
(Connection of an external timer to switch over the
heating circuit mode)
SP08
2
(Connection of a room operating unit EGT333 with
room sensor)
SP09
3
(Room temperature connection is enabled if
TRi <> TRs)
SP13
1
(Return temperature recording is enabled)
SP20
120
(Runtime for second final control element, i.e. in this
case for the final control element for fixed value control)
SP27
90
(Maximum limit for return temperature during DHW
Heating, i.e. with this control model, for fixed value
control
)
SP28
3
(Intervention intensity for violation of return temperature
limit value).
Содержание EQJW145
Страница 1: ...EQJW145 Heating controller Operating manual 7010015003 A R ...
Страница 8: ...EQJW145 Heating controller Symbols used in this manual 8 7010015003 A Fr Sauter AG ...
Страница 10: ...EQJW145 Heating controller General information 10 7010015003 A Fr Sauter AG ...
Страница 46: ...EQJW145 Heating controller Commissioning 46 7010015003 A Fr Sauter AG ...
Страница 78: ...EQJW145 Heating controller Communication functions 78 7010015003 A Fr Sauter AG ...
Страница 82: ...EQJW145 Heating controller Faults 82 7010015003 A Fr Sauter AG ...
Страница 90: ...EQJW145 Heating controller Economy tips 90 7010015003 A Fr Sauter AG ...
Страница 92: ...EQJW145 Heating controller Resistance values for the Ni1000 sensors 92 7010015003 A Fr Sauter AG ...
Страница 94: ...EQJW145 Heating controller Dimension drawing 94 7010015003 A Fr Sauter AG ...
Страница 100: ...EQJW145 Heating controller Technical data 100 7010015003 A Fr Sauter AG ...