EQJW145: Heating controller
Using the controller
86
7010015003 A
© Fr. Sauter AG
PI
2P
Fig. 9: EQJW 145 control model 1
Weather-compensating flow temperature control (secondary) in converter
installations with DHW preparation using 2 charge pumps via an additional
converter, and controller of the heating temperature for the DHW (tank
charge system)
Main SERVice parameters (see also 3.3):
SP06
2
(Control model
)
SP08
1
(Room sensor input used as 2nd flow sensor for the
DHW)
SP34
2
(DHW preparation with separate charge pump using
two DHW sensors)
SP39
-30
(Limit value for the outdoor temperature at which DHW
heating takes place with priority or in parallel
)
SP49
2
(Configurable output is used to activate a 2nd charge
pump)
Содержание EQJW145
Страница 1: ...EQJW145 Heating controller Operating manual 7010015003 A R ...
Страница 8: ...EQJW145 Heating controller Symbols used in this manual 8 7010015003 A Fr Sauter AG ...
Страница 10: ...EQJW145 Heating controller General information 10 7010015003 A Fr Sauter AG ...
Страница 46: ...EQJW145 Heating controller Commissioning 46 7010015003 A Fr Sauter AG ...
Страница 78: ...EQJW145 Heating controller Communication functions 78 7010015003 A Fr Sauter AG ...
Страница 82: ...EQJW145 Heating controller Faults 82 7010015003 A Fr Sauter AG ...
Страница 90: ...EQJW145 Heating controller Economy tips 90 7010015003 A Fr Sauter AG ...
Страница 92: ...EQJW145 Heating controller Resistance values for the Ni1000 sensors 92 7010015003 A Fr Sauter AG ...
Страница 94: ...EQJW145 Heating controller Dimension drawing 94 7010015003 A Fr Sauter AG ...
Страница 100: ...EQJW145 Heating controller Technical data 100 7010015003 A Fr Sauter AG ...