EQJW145: Heating controller
Using the controller
7010015003 A
85
© Fr. Sauter AG
AB
A
B
UP
LP1
PI
Fig. 8: EQJW 145 control model 1
Weather-compensating flow temperature control (secondary) in converter
installations with priority DHW switching via diverter valve.
Main SERVice parameters (see also 3.3)
SP06
1
(Control model
)
SP13
1
(Return temperature recording enabled)
SP20
120
(Runtime for the 2nd final control element, i.e. the
diverter valve in this case)
SP28
5
(Intervention intensity for violation of limit value for
return temperature
)
SP34
3
(DHW preparation with diverter valve using one DHW
sensor)