Description of parameters
2 - 43
7000928003 R4
Sauter Components
Yc.
Calculated positioning signal
Access:
Manual, automatic
Calculated controller output in 0...100 %; this is converted into a positioning signal of either 0...10 V or 2...10 V.
YM
Ymin-selection / Ymax-selection
Access:
Service level
Positioning signals Yc2 and Yc3 are only available if they are linked by selection. Maximum selection can also be achieved by
externally connecting control outputs in parallel. By connecting an EXG100 active potentiometer in parallel with a control out-
put, the minimum fresh-air content (for example) can be set externally.