46.102/1
flexotron
®
300
Sauter
Components
RDT 300: Electronic controller for ventilation and air-conditioning
How energy efficiency is improved
Top quality algorithm for generation of c/o signal for changeover between heating and cooling mode,
and therefore ensuring energy saving operation of the system.
Areas of application
Weather-compensated flow temperature control in 2- and 4-pipe systems for heating/cooling. Activa-
tion of intelligent unitary controllers.
Features
•
Clearly-laid-out operating unit with large LCD display and generously proportioned keypad
•
6 controller models
•
Plug-in memory for copying and documenting system parameters
•
Fast commissioning thanks to preset parameters
•
Room user panel with display available as accessory
•
Weekly and annual switching program
•
Automatic summertime/wintertime changeover
•
Sealable sliding switch for selection of operating mode
Technical description
•
Housing 144 x 96 mm made of flame-retardant, pure white thermoplastic (RAL 9010)
•
4 universal inputs and 2 analogue inputs
•
2 independent PI controllers
•
3 continuous outputs and 6 relay outputs
•
Reset, sequencing and limiting functions, as well as alarm and time functions
•
Suitable for fitting on walls, in panels and on top-hat rails
•
Electrical connection in base with screw terminals for wires up to 2.5 mm²
PI
Y06366
Type
1)
Setting range
°C
Control modes
Power supply
Weight
kg
RDT 300 F001
–30...150
P, PI
230 V~
0,67
Ranges (depend-
ing on transmitter)
Temperature
°C or K
Percentage
%
Rel. humidity
%rh
Abs. humidity
g/kg
Enthalpy
kJ/kg
No unit of
measurement
Setpoint Xs –30...150
°C
0...100
0...100 0.0...20 0...100 –4999...4999
P-band 0.1...180
K
0.1...200 0.1...100 0.1...100 0.1...100 10...4999
4 universal inputs
3)
2 analogue inputs
Temperature
Ni1000 (DIN 43760)
2
×
temperature
2) 3)
Ni1000 (DIN 43760)
Voltage
0(2)...10 V; R
i
= 100 k
Ω
0...1 V, R
i
= 500 k
Ω
Outputs
3)
Current
0(4)...20 mA, R
i
= 50
Ω
3 continuous
0(2)...10 V, load > 5 k
Ω
Potentiometer
2 k
Ω
(min.1 k
Ω
)
4 relays
5(2) A, 250 V~
2 relays
5(2) A, 24/250 V~
Power supply
230 V~ +10/–15%; 50...60 Hz
Degree of protection
IP 30 (EN 60529)
Power consumption
5 VA
Protection class F001 230V II (IEC 60730)
P-band X
p
0,1....180
K
Integral action time T
n
0....9990 s
Wiring diagram
A09432
Dimension
drawing
M368900
Cycle time
1 s
Fitting instructions
MV 505711
Permissible ambient temp. 0...45 °C
Operating instructions
Ambient humidity
5...80 %rh
For end users
7000927 (Part 1)
non-condensing
Commissioning
7000928 (Part 2)
Accessories
RDB 300
Remote-control unit see Section 46
0313516 . . .
Additional operating instructions (7000927 and 7000928)
German 001, French 002, English 003, Italian 004.
0369746 001
Cover plate for the whole front; of transparent thermoplastic; sealable
0226187 002
*
Plug-in dummy for memory slot
0226187 003
*
Plug-in memory for
flexotron
*)
Dimension drawing or wiring diagram are available under the same number
1)
Since several languages are available, please order the operating instructions as an accessory.
2)
Can also be used as a binary input (gold contacts).
3)
Protected against short-circuiting and excess voltage up to 24 V a.c. Current input for max 70 mA.
7146102003 04