Troubleshooting 
 

Issue:

 

There is no indication from the device when power is applied, and no response to pressing the 
front panel button.

 

Actions: 

 

 

Verify that the device is wired according to the instructions in Section 5.2. Ensure that the 
live source is disconnected before connecting the meter. 

 

Verify that all upstream switches and protection devices are in their closed configuration. 

 

If one or more other devices are to be installed in the same location, install another device 
to compare. If other devices function correctly, remove the non-functioning device. 

Issue:  

When performing the steps outlined in the Commissioning section of the Commissioning and 
Installation Instructions, the device does not successfully connect (indicated by button flashing 
amber for several seconds).

 

Actions: 

 

 

Ensure that ‘Permit Joining' mode is enabled on the ZigBee Coordinator (If using an ESBox, 
use the LSSS button sequence on the ESBox to enable ‘Permit Joining’ mode).

 

 

Try to join the device again 

 Saturn South metering devices will initially scan a reduced 

subset of the full range of available ZigBee channels. If the network is on a channel that is 

not in the ‘preferred channels’ list, the meter will initially fail to locate the network. A 

second join attempt will then cause the meter to scan the full set of channels. 

 

Check the RF environment to ensure the ESBox and Mini CT Meter can communicate - 
contact Saturn South for more information. 

Issue: 

 

Device stops communicating to the site ESBox.

 

Actions: 

 

 

Verify that other nearby devices are still communicating successfully with the site ESBox 
(normally, this can be done by checking for recent data in the ESCo client or management 
tools) 

 

If this is a standalone device, or if other nearby devices are also not functioning, perform a 
radio test in the deployment environment to verify that the device is in range of the ESBox 
radio. 

 

If the device exhibits abnormal behaviour (e.g. device does not respond to button presses, 
does not give button LED indications described in the Quick Reference guides in this 
manual) please contact Saturn South.

 

 

Содержание SS9007.2 Mini

Страница 1: ...D401 2 5 30 Dec 2015 SS9007 2 Mini CT Meter User Manual Version 5 Std HA Release build 5977...

Страница 2: ...Specifications 6 5 Commissioning and Installation Instructions 7 5 1 Before Installation 7 5 2 Installation 7 5 3 Commissioning 11 6 Switching 12 7 Metering 13 8 Device Clusters and Attributes 14 8 1...

Страница 3: ...ent failure This product is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience or knowledge unless they have been given super...

Страница 4: ...ill join any ZigBee HA network with Permit Joining mode enabled When the button is pressed the button colour will change to yellow and then begin to rapidly blink green once is has been held long enou...

Страница 5: ...ss 1 with a customizable reporting frequency of up to 1Hz Import export energy accumulations and true signed power measurements make the SS9007 an ideal choice for monitoring renewable generation sour...

Страница 6: ...Range 25 C to 80 C Relative Humidity 10 95 non condensing Average Power Consumption 1W Mass 0 080kg Dimensions 60 5 x 90 x 17 5mm Wire gauge 0 1mm2 min 2 5mm2 stranded or 2 5mm2 solid core max IP Rati...

Страница 7: ...Commissioning Wire the device into the switchboard as per the guidelines below and apply power 5 2 Installation The SS9007 Mini CT Meter is designed to be straightforward to install into a standard do...

Страница 8: ...terminals 5 Clip the CT on to the target load conductor ensuring that the arrow on the CT points towards the load or generator away from the grid Connect the output of a MCB RCD or other protection de...

Страница 9: ...connected in the correct polarity to ensure proper operation The Live terminal Neutral terminal two Current Transformer CT terminals CT BLACK and CT WHITE and two SWITCH terminals are marked on the s...

Страница 10: ...monitoring 7 If your Mini CT Meter has switching capability the two terminals marked SWITCH are connected internally to an isolated relay rated for 5A at 240V The front panel button will glow amber t...

Страница 11: ...econd window devices may be joined to the network by repeating step 2 If this site is being commissioned for the first time it is recommended that a factory reset be performed on the ESBox before acti...

Страница 12: ...to a digital IO on a control device such as a PLC The example below shows a SS9007 Mini CT Meter being used to control an external contactor with a 240V coil by switching the active input to the conta...

Страница 13: ...plied CT IMPORTANT Attaching a third party CT to the device can damage the device and will void the product warranty SS9007 Mini CT Meter devices have a variant label on the front panel that describes...

Страница 14: ...not be possible for a device to send 11 attributes in a single report If the total size of the report exceeds the maximum payload size 60 bytes some attributes will be excluded from the report The de...

Страница 15: ...the Simple Metering Cluster on endpoint 10 0x0A Attr ID Attr ID Hex Attribute Name Units Divisor Writeable 57610 e10a Voltage 1 RMS Mean V 100 N 57628 e11c Current 1 RMS Mean A 100 N 57646 e12e Power...

Страница 16: ...mit Joining mode Try to join the device again Saturn South metering devices will initially scan a reduced subset of the full range of available ZigBee channels If the network is on a channel that is n...

Отзывы: