Satronic MMG 810.1 Скачать руководство пользователя страница 1

1

A Honeywell Company

MMG 810.1 / 811.1

For 2-stage forced draught and combi oil/gas
burners

Suitable flame detectors:
- Ionisation probe
- UV sensor
- Infra-red flicker detector

INTRODUCTION

The MMG burner control box is capable of controlling
and monitoring forced draught and combi oil/gas burners
of any nominal rating (tested and approved as per EN 298).
The MMG 810.1 model 33 control boxes are also suitable for
use in stationary warm air generators (Direct air heaters
according to DIN 4794).
Different type and model designations identify the control
boxes according to varying national standards, and to some
extent, according to programme times.

TYPES AVAILABLE

MMG 810.1

Mod. 32

Art. Nr. 0640120

Mod. 33

Art. Nr. 0640220

Mod. 43

Art. Nr. 0642520

Mod. 45

Art. Nr. 0642620

MMG 811.1

Mod. 33

Art. Nr. 0640520

Mod. 63

Art. Nr. 0640420

ONSTRUCTIONAL FEATURES

The control box is enclosed in a protective, flame resistant,
transparent, plug-in type plastic housing, and includes:
– Synchronous motor with reduction gearing driving cam

switch

– Cam switch with informative, coloured programme in-

dicator

– 12-way cam switch assembly controlling the programme

sequence

– Electronic components on plug-in printed circuit

The following important indicators and operating controls
are situated on the front of the control box:
– Reset button incorporating signal lamp for malfunction

(lockout)

– Coloured programme indicator
– Central screw fastening

Burner Control Box

TECHNICAL DATA

Supply voltage

220 / 240 V (-15... +10%)
50 Hz (50 - 60 Hz)

AC frequency variations

result in proportional timing
deviations

Fuse rating

max. 10 A rapid, 6 A slow

Power consumption

10 VA

Max. current per output
term. 3

2A, cos 

ϕ 

0.2

term. 4, B

2A, cos 

ϕ 

0.4

term. 5, 6, C

1A, cos 

ϕ 

0.4

Total load

5A, cos 

ϕ 

0.4

Amplifier sensitivity

µ

A

Min. current from UV tube
or ionisation probe

µ

A

Flame detector cable

max. 20 m cable length

Air proving switch

1 terminal 4 A, 230 V

Reset delay

none

Flame detector
- Ionisation probe
- Infra-red flicker detector

IRD 1020.1 end-on

- UV tube type

UVZ 780 red markings
installed radially or axially

Infra red flare detector

IRD 1020

Weight incl. base

350 g

Mounting attitude

any

Insulation standard

IP 44

Permissable ambient temp.

-20

°

 C... +60

°

 C

Classified acc. to EN 298

BTLLXN

For external resetting, the remote reset device FR 870
(art. No. 70700) can be utilized. (Refer to doc. 750).

program timings (sec.)

MMG 810.1

811.1

Model

32

33

43

45

33

63

Waiting time
at start-up

 tw

9

9

9

9

9

6

Max. reaction
time for air
proving switch

tlw

6

6

6

6

6

5

Pre-purge time

tv1

24

24

40

40

24

55

Pre-ignition time tvz

3

3

3

3

3

3

T. ignition time

tz

6

6

6

8

6

5.5

Safety time

ts

2

3

3

5

3

3

Time delay
term.6 / term.C

tv2

10

10

10

10

10

6

EN1C-0142SZ20 0305

Содержание MMG 810.1

Страница 1: ...rols are situated on the front of the control box Reset button incorporating signal lamp for malfunction lockout Coloured programme indicator Central screw fastening Burner Control Box TECHNICAL DATA Supply voltage 220 240 V 15 10 50 Hz 50 60 Hz AC frequency variations result in proportional timing deviations Fuse rating max 10 A rapid 6 A slow Power consumption 10 VA Max current per output term 3...

Страница 2: ... as per IP 44 standard unaffected by water spray The control box and detector probes should however not be subjected to excessive vibration The applicable installation regulations must be observed during installation COMMISSIONING AND MAINTENANCE 1 Important Thewiringmustbecheckedexactlywhencommissioning theinstallation Incorrectwiringcoulddamagethecontrol box putting the safety of the burner syst...

Страница 3: ...GRAM AND PROCESS DIAGRAM MMG 810 1 SCHEMATIC CONNECTION DIAGRAM AND PROCESS DIAGRAM MMG 811 1 for ign spark detection only HS Mains switch GW Gas pressure switch ST Limit thermostat RT Control thermostat IS Ionisation probe UV UV sensor Z Ignition M Burner motor V1 Solenoid valve 1st stage V2 Solenoid valve 2nd stage LW Air pressure monitor SA External lock out signal for spark detection only SV S...

Страница 4: ... ORDERING INFORMATION ITEM DESIGNATION ITEM NO Control box Type MMG 810 1 mod 33 0640220 or Type MMG 811 1 mod 33 0640520 Socket Wiring base S98 12 pin 75310 Slide in plate Cable terminal plate 70502 or PG plate 70503 Flame detector IRD 1020 1 end on viewing 16552 Flame detector UVZ 780 red 18813 IRD mounting flange IRD Holder M93 59093 UVZ mounting flange UVZ Holder 18807 Flame detector cable 3 w...

Отзывы: