26
KNX-BSA12L
• KNX-BSA12H
SATEL
Reaction on rain alarm
– position to which the blind/shutter will be set in response to
a
change of state of the “Rain alarm” communication object (no reaction / fully opened /
fully closed / stop).
Reaction on wind alarm
– position to which the blind/shutter will be set in response to
a
change of state of the “Wind alarm” communication object (no reaction / fully opened /
fully closed / stop).
After the weather alarm is called off, the blind/shutter will remain in the position set,
until the position is changed by the next telegram from the bus.
Position forcing
You can define the position to which the blind/shutter will be set in response to a change of
state of the
“Forced position” communication object. When the object assumes the value “1”,
the blind/shutter will be set to the position defined, and the channel will be locked. Unlocking
of the channel is only possible when the object assumes the value
“0”. When unlocked, the
blind/shutter does not return to the position in which it was before locking. This function can
set the blind/shutter to the upper or lower end position, or stop it in the current position.
For each type of blind/shutter, reaction to the position forcing function is defined in the same
way.
The position forcing function has the highest priority. Position that will be set by this
function cannot be changed by other functions activated in the module.
Description of parameters
Channel reaction to forced position
– position to which the blind/shutter will be set in
response to a change of state of the “Forced position” communication object (fully opened
/ fully closed / stop).
4.4 Communication objects
4.4.1 Global objects