60 Programming
SATEL
– the quick arming is not possible (relevant parameters in keypads settings are
automatically modified);
– the S
HOW ARM MESSAGES
option is enabled in all keypads (it cannot be disabled);
– the following options are disabled in all keypads (they cannot be enabled):
S
IGNALING TROUBLES IN PARTIALLY ARM
;
S
IGNAL NEW TROUBLE
;
A
LARM MESSAGES
:
P
ARTITIONS
;
A
LARM MESSAGES
:
Z
ONES
;
S
HOW VIOLATED ZONES
;
D
ISPLAY MODE SWITCHING
;
– it is not possible to view the status of zones, partitions, alarms, trouble memory and
current troubles by pressing and holding down the dedicated keypad keys (the
corresponding options are disabled and cannot be enabled);
– it is not possible to present information on partition status in the bottom line of keypad
display (relevant parameters in the keypad settings will be automatically modified);
– after entering the user menu by means of the service code, you will get access in the
E
VENTS
submenu to the G
RADE
3
function, which enables viewing the events required by
EN 50131 for Grade 3;
– the I
SOLATE
user function is only available to the installer;
– the S
YSTEM STATE
user function provides information about alarms, bypassed zones,
troubles and partition status (disarmed or type of armed mode).
Tamper if no communication with ABAX device (2h)
[L.no ABAX=tamp] – with this option
enabled, tamper alarm will be triggered if there is no communication with a wireless device
of the ABAX system for 2 hours.
5.4 Arming options
Warn while arming if trouble
[Arm, warn.trb.] – if this option is enabled, the user will be
informed of the existing troubles, if any, when arming the system from keypad.
Display violated/bypassed zones on arming
[Arm, view viol] – if this option is enabled, the
user will be informed of the violated / bypassed zones when arming the system from
keypad.
If the system is being armed in the "full + bypasses" mode, bypasses and violations of
the zones for which the B
YPASSED IF NO EXIT
option is enabled are not checked.
If the system is being armed in the "without interior" or „without interior and without
entry delay” mode, bypasses and violations of the 3. I
NTERIOR DELAYED
type zones are
not checked (unless the D
ELAY IN
2&3
TYPE ARMING
option is enabled for the zone).
Do not arm if tampered
[If tamper] – if this option is enabled, arming will be impossible if
a tamper is discovered.
Do not arm if battery trouble
[If batt. trbl.] – if this option is enabled, arming will be
impossible in case of a battery failure.
Required system reset after verified alarm
[If verif. al.] – if this option is enabled, arming
will be impossible after a verified alarm.
Do not arm if trouble
[If other trbl.] – if this option is enabled, arming will be impossible in
case of a trouble.
Do not arm if outputs trouble
[If outs. trbl.] – if this option is enabled, arming will be
impossible when the control panel detects that the mainboard outputs are overloaded or
devices connected to these outputs are cut off.