Satec PM175 Series Скачать руководство пользователя страница 1

 

 

 

Quick Start

 

Guide

 

 

PM175 Series

 

Powermeter

 

 

 

 

 

 

 

 

BG0456 REV.A2 

 

Содержание PM175 Series

Страница 1: ...Quick Start Guide PM175 Series Powermeter BG0456 REV A2 1...

Страница 2: ...this quick start guide to prepare the units for operation If you are not familiar with the PM175 read the Installation and Operation Manual carefully before installing and using the unit This quick st...

Страница 3: ...Figure 2 ANSI 4 round cutout Mounting the display unit Figure 3 DIN 92x92mm square cutout Mounting the display unit BG0456 REV A2 3...

Страница 4: ...PM175 Quick Start Guide Figure 4 Slide and position the meter on locating studs Figure 5 Affix the meter using the thumb nuts please do not over tighten the nuts BG0456 REV A2 4...

Страница 5: ...NALOG INPUTS ANALOG IN OUT 1mA 0 20mA 4 20mA 0 1mA CALIBRATED AT 25 Hz 60 Hz 50 Hz 400 Hz COM 1 RS 232 422 485 STANDARD ETHERNET MODEM PROFIBUS 690V OPT U STANDARD CT 5A Figure 6 Connections and Termi...

Страница 6: ...typical installations of the PM175 Figure 7 Typical Installation 2 The typical installation diagram above shows a 4 Wire Wye 3 element connection using 3 PTs and 3 CTs The wiring mode is 4LL3 or 4Ln3...

Страница 7: ...or a remote powered display Refer to the Installation and Operation Manual for the wiring schematic diagrams Pinout for a self powered remote display PM175 D15 Female Pinout Signal Remote Display D15...

Страница 8: ...display The SELECT button operates once it s released The button has two functions o When pressed briefly switches to programming mode o When pressed together with the ENTER button for more than 5 sec...

Страница 9: ...he remaining password digits in the same manner 4 Press ENTER to confirm the password If the password entered is correct you move to the Main menu otherwise you return to the previous menu Basic Confi...

Страница 10: ...2 3OP3 and 3DIR modes voltage Used as a reference voltage for the EN50160 evaluation Ct CT primary current 1 20 000 A 5 A The primary rating of the phase current transformer d P Power block demand per...

Страница 11: ...n Prot Communications protocol ASCII rtu dnP3 ASCII Modbus RTU or DNP3 0 protocol rS Port Interface depends on order 232 RS 232 485 RS 485 422 RS 422 dial Dial up Modem Eth Ethernet For non serial int...

Страница 12: ...PM175 Quick Start Guide 05 12001 3 AC0140 Figure 10 COM1 Telephone Line Connection AC0139 05 12001 4 RJ45 Figure 11 COM1 Ethernet Connection BG0456 REV A2 12...

Страница 13: ...0 V optional INPUT USING PT Nominal 120V line to line voltage 144V maximum Burden 0 04 VA Voltage input terminals Maximum wire section 4 mm2 10 AWG 3 current inputs Galvanically isolated 5A standard I...