66
Address Point
ID
Description
Options/Range Units
Type
R/W
Notes
EGD Producer Exchanges Setup
50454-50837
+0-1
Exchange consumer IP Address
0x01000000-0xFFFFFFFF UINT32
R/W
Network byte order
+2 Production
interval
1-60000
×
10 ms
UINT16 R/W
+3
Exchange status
0=disabled, 1=enabled
UINT16
R/W
+4,5 Reserved
0
UINT16
R/W
+6
Address range #1: Start point ID
0-65535, 0=end of the range list
UINT16
R/W
+7
Address range #1: End point ID
1-65535
UINT16
R/W
+8
Address range #1: Data type
0=Word, 1=DWord, 2= Float
UINT16
R/W
+9
Address range #2: Start point ID
0-65535, 0=end of the range list
UINT16
R/W
+10
Address range #2: End point ID
1-65535
UINT16
R/W
+11
Address range #2: Data type
0=Word, 1=DWord, 2= Float
UINT16
R/W
…
R/W
+93
Address range #30: Start point ID
0-65535, 0=end of the range list
UINT16
R/W
+94
Address range #30: End point ID
1-65535
UINT16
R/W
+95
Address range #30: Data type
0=Word, 1=DWord, 2= Float
UINT16
R/W
50454-50549
Exchange #1
50550-50645
Exchange #2
50646-50741
Exchange #3
50742-50837
Exchange #4
DNP Options Setup
51158-51183
+0
Default Binary Input Static object variation
F24 (default 0)
UINT16
R/W
+1
Default Binary Input Change object variation
F24 (default 1)
UINT16
R/W
+2
Default Binary Counter object variation
F24 (default 3)
UINT16
R/W
+3
Default Frozen Binary Counter object variation
F24 (default 4)
UINT16
R/W
+4 Reserved
UINT16
R/W
+5
Default Binary Counter Change Event object variation F24 (default 2)
UINT16
R/W
+6
Default Analog Input object variation
F24 (default 3)
UINT16
R/W
+7 Reserved
UINT16
R/W
+8 Reserved
UINT16
R/W
+9
Default Analog Input Change Event object variation
F24 (default 2)
UINT16
R/W
+10
Re-mapping static point indices for event objects
0=disabled (default), 1=enabled
UINT16
R/W
+11
16-bit BC Scaling
0=
×
1 (default), 1=
×
10, 2=
×
100,
3=
×
1000
UINT16
R/W
+12
16-bit AI Scaling
0=disabled, 1=enabled (default)
UINT16
R/W
+13
Number of points allocated for Analog Input change
events
0 to 64 (default 32)
UINT16
R/W
+14
Number of points allocated for Binary Input change
events
0 to 32 (default 0)
UINT16
R/W
+15
Number of points allocated for Binary Counter change
events
0 to 64 (default 0)
UINT16
R/W
+16
Select/Operate Timeout
2 to 30 seconds (default 10 sec)
UINT16
R/W