51
3.5 Minimum/Maximum Log Registers
Address Point
ID
Description
Options/Range/Format
2
Units
2
Type R/W
Notes
35840-35959
Minimum Phase Values
+0,1
+2,3
0x2C00
Min. V1/V12 Voltage
Timestamp
0-Vmax
F1
U1
sec
UINT32
UINT32
R
R
1
+4,5
+6,7
0x2C01
Min. V2/V23 Voltage
Timestamp
0-Vmax
F1
U1
sec
UINT32
UINT32
R
R
1
+8,9
+10,11
0x2C02
Min. V3/V31 Voltage
Timestamp
0-Vmax
F1
U1
sec
UINT32
UINT32
R
R
1
+12,13
+14,15
0x2C03
Min. I1 Current
Timestamp
0-Imax
F1
U2
sec
UINT32
UINT32
R
R
+16,17
+18,19
0x2C04
Min. I2 Current
Timestamp
0-Imax U2
sec
UINT32
UINT32
R
R
+20,21
+22,23
0x2C05
Min. I3 Current
Timestamp
0-Imax U2
sec
UINT32
UINT32
R
R
+24-71 0x2C06-
0x2C11
Not used
0
INT32
R
+72,73
+74,75
0x2C12
Min. V1/V12 Voltage THD
Timestamp
0-9999
×
0.1%
sec
UINT32
UINT32
R
R
1, 3
+76,77
+78,79
0x2C13
Min. V2/V23 Voltage THD
Timestamp
0-9999
×
0.1%
sec
UINT32
UINT32
R
R
1, 3
+80,81
+82,83
0x2C14
Min. V3/V31 Voltage THD
Timestamp
0-9999
×
0.1%
sec
UINT32
UINT32
R
R
1, 3
+84,85
+86,87
0x2C15
Min. I1 Current THD
Timestamp
0-9999
×
0.1%
sec
UINT32
UINT32
R
R
3
+88,89
+90,91
0x2C16
Min. I2 Current THD
Timestamp
0-9999
×
0.1%
sec
UINT32
UINT32
R
R
3
+92,93
+94,95
0x2C17
Min. I3 Current THD
Timestamp
0-9999
×
0.1%
sec
UINT32
UINT32
R
R
3
+96,97
+98,99
0x2C18
Min. I1 K-Factor
Timestamp
10-9999
×
0.1
sec
UINT32
UINT32
R
R
3
+100,101
+102,103
0x2C19
Min. I2 K-Factor
Timestamp
10-9999
×
0.1
sec
UINT32
UINT32
R
R
3
+104,105
+106,107
0x2C1A
Min. I3 K-Factor
Timestamp
10-9999
×
0.1
sec
UINT32
UINT32
R
R
3
+108,109
+110,111
0x2C1B
Min. I1 Current TDD
Timestamp
0-1000
×
0.1%
sec
UINT32
UINT32
R
R
3
+112,113
+114,115
0x2C1C
Min. I2 Current TDD
Timestamp
0-1000
×
0.1%
sec
UINT32
UINT32
R
R
3
+116,117
+118,119
0x2C1D
Min. I3 Current TDD
Timestamp
0-1000 x0.1%
sec
UINT32
UINT32
R
R
3