Chapter 4 Setup Menus
22
4.2 Communications Port Setup Menu
This menu allows you to access the communications port options that the
C191HM
uses to communicate with a master computer. Table 4-2 lists the
communications options, their code names and applicable choices.
Activate the middle window to scroll through the list of available options, and
then activate the lower window to set the option value.
To select and view a setup option:
Press to activate the middle window.
Use the up/down arrow keys to scroll to the desired option. The option
setting will appear in the lower window.
To change the selected option:
Press to activate the lower window.
Press the up/down arrow keys to scroll to the desired value.
Press to store the selected value or press to quit the setup
menu.
Table 4-2 Communications Options
(
∗
default setting)
Code
Parameter
Options
Description
Prot
Communications
protocol
ASCII
∗
rtu
ASCII protocol
Modbus RTU protocol
Addr
Address
0
∗
-99 ASCII
1
∗
-247 Modbus
Powermeter address
bAud
Baud rate
110
110 baud
300
300 baud
600
600 baud
1200
1200 baud
2400
2400 baud
4800
4800 baud
9600
∗
9600 baud
19.20
19,200 baud
dAtA
Data format
7E
7 bits, even parity
8n
∗
8 bits, no parity
8E
8 bits, even parity
CPtb
ASCII compatibility
mode
diS
∗
, En
Disables/enables ASCII
compatibility mode. For more
information, see ASCII
Communications Protocol
Reference Guide
SELECT
Port
ASCII
Prot
SELECT
ENTER
ESC
SELECT
CHG
ENTER
Port
ENTER