7-2. Refrigerant Tubing
7-2-1. Use of the Flaring Method
Many of the conventional split system air conditioners
employ the flaring method to connect refrigerant tubes
which run between indoor and outdoor units. In this
method, the copper tubes are flared at each end and
connected with flare nuts.
7-2-3. Flaring Procedure with a Flare Tool
a)
Cut the copper tube to the required length with a
tube cutter. It is recommended to cut approx. 30 –
50 cm longer than the tubing length you estimate.
b)
Remove burrs at the end of the copper tube with a
tube reamer or file. This process is important and
should be done carefully to make a good flare.
(Fig. 7)
When reaming, hold the tube end downward and be
sure that no copper scraps fall into the tube. (Fig. 8)
c)
Remove the flare nut from the unit and be sure to
mount it on the copper tube.
d)
Make a flare at the end of copper tube with a flare
tool.
*
(Fig. 9)
(
*
Use “RIGID” or equivalent.)
e)
Use the special flare tool for R410A for making a
flare. If the conventional flare tool for R22 is uti-
lized, use the spacer provided. (Fig. 10)
A good flare should have the following characteristics:
●
inside surface is glossy and smooth.
●
edge is smooth.
●
tapered sides are of uniform length.
7-2-4. Caution before Connecting Tubes
Tightly
a)
Be sure to apply a sealing cap or water-proof tape
to prevent dust or water from getting into the tubes
before they are used.
b)
Be sure to apply refrigerant lubricant to the match-
ing surfaces of the flare and union before connect-
ing them together. This is effective for reducing gas
leaks. (Fig. 11)
c)
For proper connection, align the union tube and
flare tube straight with each other, then screw on
the flare nut lightly at first to obtain a smooth
match. (Fig. 12)
NOTE
NOTE
Where the R410A
flare tool is used
1.2 mm
Spacer
Where the conventional flare tool
is utilized (clutching method)
Flare nut
Union
Fig. 12
By using the spacer, the pipe must be adjust-
ed so that 1.2 mm of the pipe protrudes.