4-67
W-3WAY ECO-i SYSTEM Unit Specifi cations
1
2
3
4
5
6
7
8
6. Ceiling-Mounted Type (T Type)
Unit specifi cations (B)
MODEL No.
Indoor Unit
THX1852
SOURCE
208 - 230 V / 1ø / 60 Hz
PERFORMANCE
Cooling
Heating
Capacity
BTU / h
19,000
21,000
kW
5.6
6.3
Air circulation (Hi / Me / Lo)
CFM
450 / 390 / 320
Moisture removal (High)
Pints / h
4.23
–
ELECTRICAL RATINGS
Voltage rating
V
208
230
208
230
Available voltage range
V
187 - 253
187 - 253
Running amperes
A
0.15
0.14
0.15
0.17
Power input
W
16
16
16
18
Power factor
%
51
50
51
46
Max. starting amperes
A
2
2
2
2
FEATURES
Controls
Microprocessor
Fan speeds
3 and Automatic control
Air filter
Washable, easy access, long life (2,500hr)
Refrigerant control
Electronic expansion valve
Operation sound (Hi / Me / Lo)
dB-A
36 / 33 / 30
Refrigerant tubing connections
Flare type
Refrigerant tube di-
ameter
Narrow tube
in. (mm)
1 / 4 (6.35)
Wide tube
in. (mm)
1 / 2 (12.7)
Drain connection
25 A, OD 1-1 / 32”
Remote controller
Optional (RCS-TM80BG, RCS-TRP80AAB.WL)
Refrigerant tubing kit / Accessories
Optional / –
Color (Approximate value)
Munsell 10Y 9.0 / 0.4, RAL 9010-GL
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height
in. (mm)
8-1 / 4 (210)
11 (280)
Width
in. (mm)
35-7 / 8 (910)
37-3 / 4 (958)
Depth
in. (mm)
26-3 / 4 (680)
30-3 / 4 (780)
Net weight
lbs. (kg)
46 (21)
Shipping weight
lbs. (kg)
53 (24)
Shipping volume
ft
3
(m
3
)
7.6 (0.215)
Rated conditions
Colling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
TD831139̲Sec4̲p66-89.indd 67
TD831139̲Sec4̲p66-89.indd 67
2008/04/09 19:22:46