INSTALLATION GUIDE
MODULAR SUNWAY TG
TE OD
Rev. 03
– 01/06/2018
63/
139
16
External interface protection input.
Short-circuiting the two terminals enables power
delivery.
Make a jumper if unused.
Connect to a voltage-free contact if used.
17
EMERGENCY
BUTTON STATUS
Emergency button status
The two terminals:
•
Voltage-free contact closed when pressing the
pushbutton
•
Voltage-free contact open when the
pushbutton is not pressed
ELECTRICAL SPECIFICATIONS:
230Vac/2A 24Vdc 0.5A
18
19
INVERTER RUN
CONTROL
Inverter run control
Short-circuiting the two terminals enables power
delivery.
Make a jumper if not used.
Connect to a voltage-free contact if used.
20
6.6.3. Connection to the environmental inputs
The reference terminal board for the connection of the digital inputs and outputs is the X10 located in the
DC module (DC.X10). Two environmental sensors may be connected to each DC module.
CAUTION
Connecting different environmental sensors from the ones defined in the default
configuration must be done in accordance with the instructions given in section 0.
The non-observance of the instructions given in section 0 may cause irreversible damage
to the inverter.
NOTE
Some environmental inputs may be reserved for internal use in Sunway Skid platforms. Please
refer to the documentation of the Sunway Skid for details.