INSTALLATION GUIDE
MODULAR SUNWAY TG
TE OD
Rev. 03
– 01/06/2018
59/
139
Terminal
board
Location
Function
AC.X10
1
Self-power supply output
Without
Self-power Supply Option
: not connected
With
Self-power Supply Option
: terminal 1 is short-circuited to 3 and
terminal 2 is short-circuited to 4.
2
3
230 V
AC
auxiliary power supply (to be used when the d
Self-power
Supply Option
) is not fitted.
4
5
UPS Bypass.
Without UPS: make a jumper between 7 and 8
With UPS: leave 7 and 8 open
6
7
UPS Input
8
9
Smart String Box auxiliary power supply, dependent on
String
Monitoring
option.
6.5.1. Auxiliary power supply connection
The Sunway TG TE inverters require 230 V
AC
(+/- 10%) auxiliary power supplied dimensioned for auxiliary
consumptions defined in 12.3.
The auxiliary power supply, fed externally to the inverter, is to be connected to AC.X10-3 and AC.X10-4.
If no external power supply source is available, it can be obtained internally to the cabinet via the
Self-power
supply option
.
WARNING
If the Self-power supply option is installed, connecting an external auxiliary power supply
source is forbidden.
6.5.2. UPS connection
The SUNWAY TG TE inverters may be connected to a UPS to ensure back-up power supply via terminals
7-8 AC.X10. For the UPS dimensioning refer to the consumptions of the internal electronics. See section
Error! Reference source not found.
Factory setting envisages jumpers between X10-5 and X10-7 and b
etween X10-6 and X10-8.
If a UPS is connected, remove jumpers between X10-5 and X10-7 and between X10-6 and X10-8. Terminals
X10-5 and X10-6 are kept free, but must not be used.
Please refer to the Electrical and Mechanical Diagram.
WARNING
Connecting the UPS to terminals 5 and 6 may damage the inverter internal circuits as well
as the UPS.