Figure 11: Isolation Control Board ES942
Table 4 indicates the relationship between the position of the Rotary Switch CE1 located on the board and
the relative isolation resistance threshold values below which an alarm is generated.
The ES942 board is located inside the converter; remove the cover of the drawer housing the control board
to access the board itself.
Figure 12: Accessing the ES942 board
Rotary value
Isolation resistance value
0
30 KΩ
1
40 KΩ
2
50 KΩ
3
60 KΩ
4
80 KΩ
5
100 KΩ