INSTALLATION GUIDE
MODULAR SUNWAY TG
TE OD
Rev. 03
– 01/06/2018
135/
139
No.
Name
Description
I/O Features
DIP-switch
XMDI8
Multifunction auxiliary digital input
8
49
CMD
Digital inputs isolated 0V in
respect to control 0V
Common
50
+24V
Auxiliary power supply output for
multifunction optoisolated inputs
+24 V
51-
62
NOT USED
Table 56: Terminals available on the environmental sensors and field I/O board
12.13. Electrical specifications
ANALOGUE INPUTS
Analogue inputs configured in 0-10 V mode
Rating
Min
Typ
Max
Unit
Input impedance
40
kΩ
Cumulative offset and gain error in relation to full scale value
0.5
%
Temperature coefficient of the offset and gain error
200
ppm/°C
Digital resolution
12
bit
Voltage LSB value
2.44
mV/LSB
Permanent overload on the inputs without causing damage
-30
+30
V
Input filter cut-off frequency (low-pass first order filter)
1
Hz
Sampling period (depending on the application SW in use)
10
1000
ms
Table 57: Analogue inputs configured in 0 - 10 V mode
Analogue inputs configured in 0-20 mA mode
Rating
Min
Typ
Max
Unit
Input impedance
40
kΩ
Cumulative offset and gain error in relation to full scale value
0.5
%
Temperature coefficient of the offset and gain error
200
ppm/°C
Digital resolution
12
bit