INSTALLATION GUIDE
MODULAR SUNWAY TG
TE OD
Rev. 03
– 01/06/2018
127/
139
TG 900 1500V TE
AC
Module
Copper
bar
TG 1200 1000V TE
TG 1800 1500V TE
Table 47: Technical data for earth cables
DANGER
Always observe the regulations applicable to the installation place for the dimensioning
of the earth cables.
12.8.4. Connection of auxiliary power supply cables
The auxiliary power supply is to be connected only if the
Self-power supply option
is not installed.
Inverter Model
Terminals
Voltage/
Frequency
Power
[VA]
Minimum
allowable
cable cross-
section [mm
2
]
Maximum
allowable
cable
cross
section
[mm
2
]
TG 610 1000V TE
X10 3-4
AC
module
230Vac 50-
60Hz
2700
0.5
2.5
TG 900 1500V TE
TG 1200 1000V TE
X10 3-4
AC
module
230Vac 50-
60Hz
4000
0.5
2.5
TG 1800 1500V TE
Table 48: Technical data for auxiliary power supply cables
12.8.5. Connecting the UPS
To connect the UPS, remove the jumpers between terminals 5 and 7 and 6 and 8 in X10 in the AC module.
Inverter Model
Terminals
Voltage/
Frequency
Average
Power
[VA]
Peak
Power
(1s)
[VA]
Minimum
allowable
cable
cross-
section
[mm
2
]
Maximum
allowable
cable
cross
section
[mm
2
]
TG 610 1000V TE
X10 7-8
AC
Module
230 Vac
50-60 Hz
100
500
0.5
2.5
TG 900 1500V TE
TG 1200 1000V TE
230 Vac
150
950
0.5
2.5