SINUS PENTA
PROGRAMMING GUIDE
124
/
486
14. MULTISPEED
MENU
14.1.
Overview
NOTE
See also the INPUTS FOR REFERENCES MENU and the DIGITAL INPUTS MENU.
The Multispeed menu allows defining the values for 15
preset speed
(or
multispeed
) references set in parameters
P081
to
P098
. Their application method is set in
P080
.
The desired speed is selected through the digital inputs described in the previous section, relating to the
Digital Inputs
Menu
.
The following reference ranges that can be programmed with the parameters above:
±
32000 rpm
if multispeed unit of measure is
→
P100
= 1.00 rpm
±
3200.0 rpm if multispeed unit of measure is
→
P100
= 0.10 rpm
±
320.00 rpm if multispeed unit of measure is
→
P100
= 0.01 rpm
Use parameters
C155
,
C156
,
C157
and
C158
to set the digital inputs in multispeed mode.
Parameter
P080
defines the functionality of the references set in the preset speed function: PRESET SPEED, SUM
SPEED, EXCLUSIVE PRESET SPEED.
If
P080
=
PRESET SPEED
, the speed reference is the value set in the preset speed which is active at that moment. If
digital inputs set as
multispeed
are all open (inactive), the speed reference is the reference coming from the sources
selected in the
Control Method Menu
(
C143
to
C146
).
If
P080
=
EXCLUSIVE PRESET SPEED
, the speed reference is the value set in the multispeed which is active at that
moment. If digital inputs set as
multispeed
are all open (inactive), no other reference source is considered; the speed
reference is zero.
If
P080
=
SUM SPEED
, the speed reference value assigned to the
preset speed
which is active at that moment is
summed up to the total amount of the speed references.
The reference obtained is always saturated by the parameters relating to the min. speed and the max. speed of
the selected motor.
14.2.
List of Parameters P080 to P100
Table 28: List of parameters P080 to P100
Parameter
FUNCTION
User Level
DEFAULT VALUES
MODBUS
Address
P080
Multispeed function
BASIC
0:Preset Speed
680
P081
Output speed Mspd1
BASIC
0.00 rpm
681
P083
Output speed Mspd2
BASIC
0.00 rpm
683
P085
Output speed Mspd3
BASIC
0.00 rpm
685
P087
Output speed Mspd4
ADVANCED
0.00 rpm
687
P088
Output speed Mspd5
ADVANCED
0.00 rpm
688
P089
Output speed Mspd6
ADVANCED
0.00 rpm
689
P090
Output speed Mspd7
ADVANCED
0.00 rpm
690
P091
Output speed Mspd8
ADVANCED
0.00 rpm
691
P092
Output speed Mspd9
ADVANCED
0.00 rpm
692
P093
Output speed Mspd10
ADVANCED
0.00 rpm
693
P094
Output speed Mspd 11
ADVANCED
0.00 rpm
694
P095
Output speed Mspd 12
ADVANCED
0.00 rpm
695
P096
Output speed Mspd 13
ADVANCED
0.00 rpm
696
P097
Output speed Mspd 14
ADVANCED
0.00 rpm
697
P098
Output speed Mspd 15
ADVANCED
0.00 rpm
698
P099
Fire Mode speed
ENGINEERING
750 rpm
699
P100
Multispeed unit of measure
ADVANCED
2: 1.0 rpm
700
Содержание PENTA MARINE
Страница 173: ...PROGRAMMING GUIDE SINUS PENTA 173 486 Figure 27 Response to the step based on the value of Kp when Ti is kept constant...
Страница 196: ...SINUS PENTA PROGRAMMING GUIDE 196 486 Figure 34 ANALOG Mode Figure 35 DOUBLE DIGITAL Mode...
Страница 197: ...PROGRAMMING GUIDE SINUS PENTA 197 486 Figure 36 General structure of the parameterization of a digital output...