4/12
ASAC-0
3
Electrical Installation
3.1
Power Terminations
1/L1, 3/L2, 5/L3, 2/T1, 4/T2, 6/T3
mm
2
(AWG)
A1, A2, A3, 01, 02, 13, 14,
23, 24 mm
2
(AWG)
007 - 030
037 - 055
075 - 110
007 - 110
1
0
4
2
7
.A
10 - 35
(8 - 2)
1
0
4
2
8
.A
14 mm
(0.55 inch)
25 - 50
(4 - 1/10)
1
0
4
2
8
.A
14 mm
(0.55 inch)
N.A.
26
(1.02)
11
(0.43)
Ø 8.5
(0.33)
1
0
4
2
9
.A
mm (inch)
0.14 - 1.5
(26 - 16)
1
0
4
2
8
.A
6 mm
(0.24 inch)
Torx (T20)
3 Nm
2.2 ft-lb
Torx (T20)
4 Nm
2.9 ft-lb
n/a
n/a
7 mm
3 Nm
2.2 ft-lb
7 mm
4 Nm
2.9 ft-lb
n/a
3.5 mm
0.5 Nm max
4.4 in-lb max
3.2
Control Voltage
•
ASAC-0/xxx/x/1 (110~240 VAC): A1, A2
•
ASAC-0/xxx/x/1 (380-440 VAC): A2, A3
•
ASAC-0/xxx/x/2 (24 VAC/VDC): A1, A2
WARNING
Always apply control voltage before (or with) mains voltage.
CAUTION
With 24 VAC/VDC use contacts rated for low voltage and low current (gold flash or similar).
3.3
Control Circuits
WARNING
Isolate the ASAC-0 completely from the power supply before attempting any work on the ASAC-0 or motor. Control
terminals may be at phase voltage potential.
CAUTION
For ASAC-0/xxx/x/2 (24 VAC/VDC control voltage) units you can connect an external 24 VDC supply into the control input
terminals 01, 02.
Two-wire control
Three-wire control
110~240 VAC
&
24 VAC/VDC
A3
A1 (+)
A2 (-)
01
02
A3
A1
A2
01
02
1
1
03241.
D
A3
A1 (+)
A2 (-)
01
02
A3
A1
A2
01
02
2
3
2
3
03242.
E
380-440 VAC
1
Start/Stop. To reset a trip, open then close 02.
2
Start.
3
Stop. To reset a trip, open then close 02.
Содержание ASAC-0
Страница 12: ...12 12 ASAC 0...