2/12
ASAC-0
1
Caution Statements
Caution Statements cannot cover every potential cause of equipment damage but can highlight common causes of damage. It is the
installer's responsibility to read and understand all instructions in this manual prior to installing, operating or maintaining the equipment,
to follow good electrical practice including applying appropriate personal protective equipment and to seek advice before operating this
equipment in a manner other than as described in this manual.
•
Isolate the ASAC-0 completely from the power supply before attempting any work on the ASAC-0 or motor.
•
Cables to the control inputs must be segregated from mains voltage and motor cabling.
•
Some electronic contactor coils are not suitable for direct switching with PCB mount relays. Consult the contactor
manufacturer/supplier to confirm suitability.
•
Do not apply incorrect voltages to the control input terminals.
CAUTION
Power factor correction capacitors must be connected to the input side of the soft starter. Connecting power factor
correction capacitors to the output side will damage the soft starter.
The examples and diagrams in this manual are included solely for illustrative purposes. The information contained in this manual is
subject to change at any time and without prior notice. In no event will responsibility or liability be accepted for direct, indirect or
consequential damages resulting from the use or application of this equipment.
WARNING – ELECTRICAL SHOCK HAZARD
The ASAC-0 contains dangerous voltages when connected to mains voltage. Only a qualified electrician should carry out the
electrical installation. Improper installation of the motor or the soft starter may cause equipment failure, serious injury or
death. Follow this manual and local electrical safety codes.
GROUNDING AND BRANCH CIRCUIT PROTECTION
It is the responsibility of the user or person installing the ASAC-0 to provide proper grounding and branch circuit protection
according to local electrical safety codes.
SHORT CIRCUIT
The ASAC-0 is not short circuit proof. After severe overload or short circuit, the operation of the ASAC-0 should be fully
tested by an authorised service agent.
1.1
Avertissements à l'attention des clients canadiens
AVERTISSEMENT
L'icône AVERTISSEMENT ci-contre signale les informations concernant des risques pouvant entraîner des blessures
graves, voire mortelles. Pour votre sécurité, veuillez consulter les avertissements sur cette page ou demander une copie du
présent manuel en français auprès de votre distributeur local.
AVERTISSEMENT - DANGER D'ÉLECTROCUTION
L’ASAC-0 contient des tensions dangereuses lorsqu'il est raccordé à l'alimentation secteur. Seul un électricien compétent
peut effectuer l'installation électrique. Une mauvaise installation du moteur ou de l’ASAC-0 peut déclencher une panne
d'équipement, provoquer de graves blessures ou même la mort. Suivre les instructions de ce manuel et des codes locaux
concernant la sécurité électrique.
AVERTISSEMENT
Toujours appliquer la tension de commande avant (ou en même temps que) la tension secteur.
AVERTISSEMENT
Isoler complètement l’ASAC-0 de l'alimentation secteur avant de tenter toute intervention sur l’ASAC-0 ou sur le moteur.
Les bornes de commande peuvent être au potentiel de la tension de phase.
Содержание ASAC-0
Страница 12: ...12 12 ASAC 0...