Description:
Selects which information will be displayed on the main monitoring screen.
10I –
User Parameter 2
Options:
Refer to parameter 10H
User Parameter 1
for details.
Default:
Motor Voltage
Description:
Selects which information will be displayed on the main monitoring screen. Refer to parameter 10H
User
Parameter 1
for details.
10J –
User Parameter 3
Options:
Refer to parameter 10H
User Parameter 1
for details.
Default:
Mains Frequency
Description:
Selects which information will be displayed on the programmable monitoring screen. Refer to parameter 10H
User Parameter 1
for details.
10K –
User Parameter 4
Options:
Refer to parameter 10H
User Parameter 1
for details.
Default:
Motor pf
Description:
Selects which information will be displayed on the programmable monitoring screen. Refer to parameter 10H
User Parameter 1
for details.
10L –
User Parameter 5
Options:
Refer to parameter 10H
User Parameter 1
for details.
Default:
Motor Power
Description:
Selects which information will be displayed on the programmable monitoring screen. Refer to parameter 10H
User Parameter 1
for details.
10M –
User Parameter 6
Options:
Refer to parameter 10H
User Parameter 1
for details.
Default:
Motor Temperature (%)
Description:
Selects which information will be displayed on the programmable monitoring screen. Refer to parameter 10H
User Parameter 1
for details.
9.15
11 Pump Clean
11A –
Reverse Torque
Range:
20% - 100%
Default:
20%
Description:
Sets the torque level for reverse jog operation during pump clean.
11B –
Reverse Time
Range:
0:00 - 1:00 (minutes:seconds)
Default:
10 seconds
Description:
Sets the time for the starter to operate in reverse jog during a pump clean cycle.
11C –
Forward Current Limit
Range:
100% - 600% FLC
Default:
100%
Description:
Sets the current limit for forward start operation during pump clean.
11D –
Forward Time
Range:
0:00 - 1:00 (minutes:seconds)
Default:
10 seconds
Description:
Sets the time for the starter to run the motor after a forward start, during a pump clean cycle.
11E –
Pump Stop Mode
Options:
Coast To Stop (default)
TVR Soft Stop
Description:
Selects the stop mode for pump clean.
11F –
Pump Stop Time
Range:
0:00 - 1:00 (minutes:seconds)
Default:
10 seconds
Description:
Sets the stopping time for the starter during a pump clean cycle.