3P –
Start Delay-2
Range:
0:00 - 60:00 (minutes:seconds)
Default:
0 second
Description:
Sets a delay after the starter receives a start command, before it starts the motor.
3Q –
DC Brake Torque-2
Range:
20% - 100%
Default:
20%
Description:
Sets the amount of brake torque the ASA 4.0 Advanced will use to slow the motor.
3R –
DC Brake Time-2
Range:
0:01 - 0:30 (minutes:seconds)
Default:
1 second
Description:
Sets the duration for DC injection during a braking stop.
3S –
Brake Current Limit-2
Range:
100% - 600% FLC
Default:
250%
Description:
Sets the current limit for soft brake.
3T –
Soft Brake Delay-2
Range:
400 - 2000 milliseconds
Default:
400 milliseconds
Description:
Sets the time the soft starter will wait after a stop signal is received, before it begins to supply braking current to
the motor. Set to allow time for K1 and K2 to switch.
9.8
4 Auto-Start/Stop
For clock mode to operate:
•
parameter 4A
Auto-Start/Stop Mode
must be set to 'Enable'
•
parameter 1A
Command Source
must be set to 'Clock'
•
the reset input must be closed
•
the start input (11, 12) must be active. This allows the ASA 4.0 Advanced to be stopped via the digital inputs in an
emergency.
Clock mode operation is controlled by parameters 4D ~ 4X.
4A –
Auto-Start/Stop Mode
Options:
Disable (default)
Enable Clock Mode
Enable Timer Mode
Description:
Enable or disable auto-start/stop operation.
4B –
Run Time
Range:
00:00 - 23:59 hh:mm
Default:
00:00
Description:
Sets the duration for the starter to run, after a timer mode auto-start.
4C –
Stopped Time
Range:
00:00 - 23:59 hh:mm
Default:
00:00
Description:
Sets the duration for the starter to remain stopped, when operating in timer mode.
4D –
Sunday Mode
Options:
Start/Stop Disable (default)
Disables auto-start/stop control. Any times scheduled in parameters 4E or 4F
will be ignored.
Start Only Enable
Enables auto-start control. Any auto-stop times scheduled in parameter 4F will
be ignored.
Stop Only Enable
Enables auto-stop control. Any auto-start times scheduled in parameter 4E will
be ignored.
Start/Stop Enable
Enables auto-start and auto-stop control.
Description:
Enables or disables auto-start/stop for Sunday.
ASA 4.0 Advanced