![Santerno ASA 4.0 Advanced Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/santerno/asa-4-0-advanced/asa-4-0-advanced_user-manual_810292031.webp)
7.4
Starter status LEDs
Ready
Run
Trip
Local
17694.
A
LED name
On
Flashing
Ready
The motor is stopped and the starter is ready to start. The motor is stopped and the starter is not ready to start:
•
waiting for the
Restart Delay
(parameter 5P)
•
the thermal models indicate the starter and/or motor
are too hot to start safely
•
the reset input (10, 11) is open
Run
The motor is in run state (receiving full voltage).
The motor is starting or stopping.
Trip
The starter has tripped.
The starter is in warning state.
Local
The starter is being controlled via a remote keypad.
–
If all LEDs are off, the starter is not receiving control voltage.
7.5
Displays
The keypad displays a wide range of performance information about the soft starter. To scroll through the feedback screens, press the
and buttons.
7.5.1
Starter information
At power-up, the starter information screen shows details of the starter's rating, software versions and serial number.
Welcome
01.01/01.00/01.00
Software versions: user interface, motor control, remote keypad
ASA4.0-A 0069B-5-S1-12
Model code: current rating, mains voltage, frame size, control voltage
(remote keypad software version is only displayed when a remote keypad is connected)
7.5.2
Starter status screen
69.0 A
motor running current
Running
Starter status
69.0 A
415 V
Parameter 10H
User Parameter 1
and parameter 10I
User Parameter 2
7.5.3
Current
The current screen shows real-time line current on each phase.
Phase Currents
000.0A 000.0A
000.0A
7.5.4
Last Start Information
The last start information screen shows details of the most recent successful start:
•
start duration (seconds)
•
maximum start current drawn (as a percentage of motor full load current)
•
calculated rise in motor temperature
Last start010 s
350 % FLC
∆
Temp 5%
7.5.5
User configurable screen
The programmable screen can be configured to show the most important information for the particular application. Use parameters 10J
~ 10M to select which information to display.
Mains Frequency 59.7 Hz
Motor pf
0.95
Motor Power
37.0 kW
Motor Temperature 85%
7.5.6
Date and Time
The date/time screen shows the current system date and time (24 hour format). For details on setting the date and time, refer to
Set
Date and Time
on page 24.
ASA 4.0 Advanced
31/78