4.3.3
Start/Stop
The ASA 4.0 Advanced requires two-wire control.
A
B
17622.
A
A
Reset
B
Start/Stop
WARNING
If the start input is closed when control voltage is applied, the starter will attempt to start.
Check that the start/stop input is open before applying control voltage.
NOTE
The ASA 4.0 Advanced will only accept commands from the control inputs if parameter 1A
Command Source
is set to
Digital Input.
4.3.4
Reset/Starter Disable
The reset input (10, 11) is normally closed by default. The ASA 4.0 Advanced will not perform a start if the reset input is open. The
display will show "Not Ready".
If the reset input opens while the ASA 4.0 Advanced is running, the starter will remove power and allow the motor to coast to stop.
NOTE
The reset input can be configured for normally open or normally closed operation. Use parameter 7I
Reset/Enable Logic
.
4.3.5
Programmable Inputs
The programmable inputs (13, 14 and 13, 15) allow external equipment to control the starter.
The operation of the programmable inputs is controlled by parameters 7A~7H.
4.3.6
USB Port
The USB port can be used to upload a configuration file, or download parameter settings and event log information from the starter.
Refer to
USB Save & Load
on page 25 for details.
4.4
Outputs
4.4.1
Output Terminals
2/T1
4/T2
6/T3
1/L1
3/L2
5/L3
B4 B5 10 11 12 13 14 15 21 22
33 34 41 42 44 53 54
A3 A1 A2
33 34 41 42 44 53 54
B4 B5 10 11 12 13 14 15
21 22
21, 22
Analog output
33, 34
Main contactor output
41, 42, 44
Relay output A (default = Run)
53, 54
Relay output B (default = Run)
18/78
ASA 4.0 Advanced