Santak CASTLE Series Скачать руководство пользователя страница 1

VALVE REGULATED SEALED LEAD ACID BATTERY 

Castle Series 

Operation and 
Maintenance 
Manual 

Содержание CASTLE Series

Страница 1: ...VALVE REGULATED SEALED LEAD ACID BATTERY Castle Series Operation and Maintenance Manual...

Страница 2: ...ack and check 5 4 2 Notices before Installation 5 4 3 Installation and connection 5 5 Use of battery 7 5 1 Supplementary charge 7 5 2 Discharge 7 5 3 Charge 8 6 Battery maintenance 11 6 1 Cleanness 11...

Страница 3: ...pecially trained by the principal Considering the potential harm of the lead component to the health and environment the battery can be replaced only by the service center authorized by the manufactur...

Страница 4: ...f the battery as it contains electrolyte that may cause injury to the human body Warning Battery may cause short circuit Please remove any watches and jewelry during replacement of the battery and ope...

Страница 5: ...e flame water and heat supply etc When storing the battery disconnect charger and load Store in dry and cool conditions After storing for any certain time please charge the batteries before use Using...

Страница 6: ...ontrolled within 3 Heat dispersing maintain 20mm inter bloc distance between batteries Ventilation Ensure batteries are stored and used in ventilated conditions Float charge 25 limited current 0 30C10...

Страница 7: ...r equipment A battery may cause flammable gas during storage avoid enclosing with any apparatus which produce flames sparks Before connecting clean the terminals to bright metal Ensure that no conduct...

Страница 8: ...terminals ensuring every connecting nut and screw is secure see torque settings as table 1 Table 1 Suggested torque table S N Range Torque 1 M5 2 0 3 0 N m 20 30kgf cm 2 M6 3 9 5 4 N m 40 55kgf cm 3 M...

Страница 9: ...s b Charging at a constant current of 0 3C A and a constant voltage of 2 30 2 40V cell for 10 16 hours c Charging at a constant of 0 1C A for 8 10 hours 20 30 Every 6 months 30 40 Every 3 months Note...

Страница 10: ...tened too low for a long time not charge enough Cannot meet load and or make battery voltages inconsistent The battery group capacity will drop accordingly and life is shortened 5 3 2 Cycle use charge...

Страница 11: ...tery without using it for more than 3 months Float voltage of battery unit is less than 2 18V cell Continuously float charging battery for 3 6 months or low voltage batteries appears in battery group...

Страница 12: ...charge end point a Charged value is not less than 1 2 times of the released value b The current is less than 0 005C10A C10 rated capacity of the battery during the final period of charging c The curr...

Страница 13: ...ve end of battery group with voltage meter 1 tested data comply with the data displayed on the meter and meet the voltage standard under the temperature conditions 2 The error of float charge voltage...

Страница 14: ...n please replace the cable and clear the connection point with a steel brush before attaching new connectors Switch DC power supply Cut off AC power supply and change to UPS or DC power supply AC powe...

Страница 15: ...ctivation charge and discharge Charge and discharge the battery by one cycle then charge the battery by the lower limit of the equalization voltage About 30 of the rated capacity is released Produced...

Страница 16: ...ied with the maintenance rules and related requirement 4 Always wear insulated gloves when handling the batteries to avoid electric shock Make sure the metal instrument is insulated 5 Use instrument a...

Страница 17: ...al parameters and site environment Please handle it in time b Check the limited charge current set is correct please adjust immediately c Check the alarm voltage below voltage and over voltage alarm o...

Страница 18: ...re the end of service life so that the application can run safely and normally 7 3 Exchange steps Step 1 Disconnect the battery s inter cell connectors and inter tier connectors Step 2 The batteries r...

Страница 19: ...is above 45V please be sure to wear insulated gloves when working otherwise there is a risk of severe electrical shock Do not bring face close to the top of batteries please keep a sensible distance w...

Страница 20: ...antak com SANTAK ELECTRONICS SHENZHEN CO LTD Address No 8 Baoshi Road Baoan District Shenzhen 518101 Tel 0086 755 27572666 Fax 0086 755 27572730 27572480 E mail Santak_int eaton com Website www santak...