6-2 Test run
(5)
Auto torque boost control
The inverter is provided with voltage compensation function and slip compensation function. The former is
used for auto-regulating the inverter output voltage, while the latter is used for slip frequency compensation
based on the load.
Use F2007 to select the above functions.
6-2-5
Basic setting (2)
Please follow the operation steps to set the following function codes.
Table 6-6 Basic function (2)
Function
Code
Name
Content
Remarks
F1005
Base voltage
200V Series 0: no AVR, 50-240V
Please check the
rated voltage
400V Series 0: no AVR, 50-460V
F1006
Base frequency
0.1-600Hz
F1007
Upper frequency limit
5-599Hz
F1009
Carrier frequency
adjustment
0-130
F1101
Operation command
selection
1.
Operation Panel
2.
External terminal
3.
Communication
F1110
Direction
of
motor
rotation
(Operation panel)
1: Forward, 2: Reverse
F1701
Output current limiting
function
Mode A (heavy overload) 0: no function 50-200
Mode B (light overload) 0: no function 50-150
F1702
Electric thermal setting
0: No function
20-105%
※
Please confirm the factory presets which can be set again only when the need for change really exists.
6-2-6
Motor parameter auto tuning
The so-called auto tuning mode is a function which automatically measures the parameters of the connected motor
which will be stored to the inverter’s memory.
This function is a useful function when it is hoped to implement vector control and auto torque control with the
motor parameters not fully known. It is also a useful function when it is hoped to implement speed control and
torque control if the distance between the inverter and motor is more than 30m.
<For F1001=10, 11 (Motor parameter auto tuning)>
The auto tuning function has two modes for selection.
Table 6-7 Auto tuning mode
Function Code F1001
Function
Motor Parameters
Remarks
10
Auto tuning mode 1: Measure
when the motor shaft is fixed
Primary resistance R1
Secondary resistance R2
Leakage inductance l
Excitation inductance M
For cases where the motor
can not operate
11
Auto tuning mode 2: Measure
when the motor is operating
Primary resistance R1
Secondary resistance R2
Self-inductance L
Excitation current I.
For cases where the motor
can operate