5-5 Special functions
5-5-5
Alarm status confirmation operation
Alarm status confirmation is a function for displaying the inverter’s status when an alarm occurs.
It can be used to confirm the latest 5 alarm statuses through function codes F1806 - F1810. If a new alarm occurs,
then the first alarm will be deleted. F1806 is the latest alarm, while the F1810 is the first alarm.
Operation example: Confirming the inverter status when the latest alarm occurs
Operation
Display
Description
Select function code F1806 (alarm status confirmation)
Press (Set) key, then the alarm name and
indicating display of [alarm name] will be displayed
alternately. The will be displayed if the alarm status is
not recorded.
After the alarm has been stored, turn the quick knob to switch
the contents displayed. Now, the detonation (*1)
and the value
(*2) when alarm occurred will be
displayed
or
Press the
(Back) key or key, then the interface will
return to function code setting.
or
Press the (Back) key or key to return to function code
selection interface.
If the function code is set to F1805 = 9, alarm records will be eliminated. At this time, all the alarm records from
F1806 to F1810 will be deleted.
*1: The denotations are shown in the table below
Denotation
Meaning
Unit
Alarm name
-
Output frequency
Hz
Output current
A
Output voltage
V
DC voltage
V
Output power
kW
Radiator temperature
℃
*2
:
The value displayed indicates the inverter status before occurrence of an alarm. Therefore, if an alarm is caused by
transient over-current or over-voltage, the stored value is somewhat different from the current value or voltage
value at the occurrence of the alarm (factors causing alarm).