SEC3002 FIRE ALARM CONTROL PANEL
Page 17 of 24
5.2.4 Disable/test functions
Besides the disable/test functions that can be carried out at access level 2, there are some
other tests designed specially for the convenience of commissioning by authorized personnel
at access level 3. They are point test, module start/stop and duplicate address check.
Check duplicate address
This function helps you to locate detector/module with duplicate addresses on the loop.
When ‘Check’ clicked, it starts checking and the buttons are of no effect during the period.
When complete, all duplicate addresses will be shown as below.
Point test
This function allows you to view the analogue status of any addressable point in real time.
When selected, you will be prompted to enter the specific address of the device you want to
put into test:
Enter the target point and press OK to start the point test:
Module start/stop
This function allows you to trigger or stop an output type module to check the module and its
following device are working correctly.
When selected, all the addresses of preregistered modules with their device type will be listed
to be chosen from.
It provides an intuitive way for device commissioning individually.
Note
: It is commonly used for
analyzing and locating faults, it will
not exit until a manual operation or
an event present, thus long time
use is not recommended.
The curve indicates the change of smoke
density in the no.47 smoke detector
during the test. Here, the background
value, alarm value and drift value only
apply to smoke detector. Press Exit to
stop at any time.