SEC1000 FIRE ALARM CONTROL PANEL

Page

8

of 24

3.7 Maximum loop cable length recommendations

To ensure a reliable system, some care must be taken when calculating the appropriate cable
gauge for the system. The main limitation is that during an alarm condition (maximum current
draw), the maximum volt drop at the end of the loop must be at least 19 Volts . The exact
calculation equations are beyond the scope of this manual, because of the distributed load of
the sounders on the loop. The following table gives a rough guide for maximum cable lengths
at various current loads for 3 different cable gauges.

MAXIMUM LOOP CURRENT(IN ALARM) 500mA

400mA

300mA

200mA

1.0mm

2

twisted-pair

cable

440m

550m

730m

1100m

1.5mm

2

twisted-pair

cable

660m

820m

1100m

1650m

2.5mm

2

twisted-pair

cable

1080m

1350m

1800m

2700m

Cable Resistance

Core Diameter

Typical Resistance

1.0mm

2

18.1 ohm/km

1.5mm

2

12.1 ohm/km

2.5mm

2

7.41 ohm/km

3.8 Other terminal connections

1.

F.A. Out

short for Fire Alarm Output: When there is a general fire the output is activated. A

47K end-of-line resistor (provided) is connected at the end of the circuit to allow the wiring to
be monitored. If the circuit is unused, the 47K resistor must still be connected. It is also
monitored for open or short circuit fault of its wiring. A typical connection is shown below.

2.

Fault Out

short for Fault Output: The NO and COM are closed in normal state. When there

is a general fault, this voltage free relay switches.

3.

S.C. Out

short for Sounder Circuit Output: A conventional sounder circuit is provided.

When there is a general fire it activates the sounders connected by default. The sounders can
be aborted and restarted by pressing the SILENCE button. It can be disabled, therefore no
output under disabled state. It is also monitored for open or short circuit fault of its wiring. A
typical connection is shown below.

Содержание SEC1000

Страница 1: ......

Страница 2: ...imum loop cable length recommendations 8 3 8 Other terminal connections 8 4 Indications and Controls 9 4 1 LED indicators 9 4 2 Button controls 10 4 3 Zone Indicators 11 5 Commissioning and Programmin...

Страница 3: ...loop of 120 addressable points and expansion capabilities It is compatible with other peripherals made by Sanjiang with its own protocol 2 2 Technical Specifications Power supply Mains supply 230VAC...

Страница 4: ...n rate 9600 bps Recommended type of cable Unscreened twisted pair 1mm2 Transmission distance 1000m Cable diameter 1mm2 2 5mm2 CAN Max number of panels 20 Transmission rate Optional 10K 20K 50K and 100...

Страница 5: ...refer to the separate manual of PMC_01 and the datasheet of Switching Power Supply for more details The P S E is an integrated unit that provides power both for the panel and the backup rechargeable...

Страница 6: ...C1000_COM PMC_01 LSP 75 24 ADJ TB4 LED TB3 DC TB2 AC TB1 AC TB5 Red Black Red Red Black Red Red Black Black Red Black Yellow green Blue Brown RS485 3 3 Mounting the chassis to the wall The panel can b...

Страница 7: ...0V 10A L N Red Black Red Black Red Red Black Black Yellow green Blue Brown To Battery 3 5 Battery connection For this single loop system 2 12V 7Ah sealed lead acid batteries are used as per the calcul...

Страница 8: ...Loop In and Loop Out terminal block on the MB Board It should be noted when the loop is in class B connection the terminal LOOP INPUT on MB Board is not available Means to limit the consequences of sh...

Страница 9: ...meter Typical Resistance 1 0mm2 18 1 ohm km 1 5mm2 12 1 ohm km 2 5mm2 7 41 ohm km 3 8 Other terminal connections 1 F A Out short for Fire Alarm Output When there is a general fire the output is activa...

Страница 10: ...d POWER FAULT Lit yellow when the panel s mains power battery or charger is in fault condition SYSTEM FAULT Lit yellow when the panel is unable to provide mandatory functions POWER Lit green to show t...

Страница 11: ...access level 2 3 Press again to resound the sounders previously silenced Silences the panel s internal buzzer COPY Copies the content of text selected currently PASTE Pastes the content of text copie...

Страница 12: ...ompletion of all the installation and connection work It includes registering and test of detectors and modules setup of the zone indication and control panel C E programming and etc All these functio...

Страница 13: ...ion rate The number of each panel should be different There are 4 transmission rates 10K 20K 50K 100K Some factors like the total number of network panels the transmission distance of the system and t...

Страница 14: ...ing function in order to avoid displaying confusion or communication error try to configure and register different zones on different networking panels Detector module setup All detectors and modules...

Страница 15: ...ct Type are kept the same as detectors Refer to the Annex device type list for all the Device Type provided in this system The Zone refers to where a device belongs in the protected premises It repres...

Страница 16: ...g In the event of a fire a default output of sounders will be activated Besides this outputs of specified modules can be set here as per requirements from the client specifier Click by the USB mouse o...

Страница 17: ...e For the function of overriding delays by activating any MCP in the system it refers to the delay which is running If the MCP used to override the delays is involved in another c e rule with a time d...

Страница 18: ...hey are point test module start stop and duplicate address check Check duplicate address This function helps you to locate detector module with duplicate addresses on the loop When Check clicked it st...

Страница 19: ...prompts below the loop learn process may take about 120s and it cannot be stopped during the period When the auto learn completes successfully a comparison between the loop learn result and the initi...

Страница 20: ...ata backup Take the prompt as reference Load data from U disk This function will load the configuration file from U disk to the panel s flash and overwrite the panel s existing data So this function m...

Страница 21: ...rating as the prompt says will complete 5 2 6 View system and software version info The system information as well as the version of each processor with program can be read through the corresponding m...

Страница 22: ...tor or a manual call point is typically 0 001A or 1mA while that of a input output modules or Intelligent Sounder Beacon is 0 008A or 8mA IRout is the alarm output current of the panel s three relays...

Страница 23: ...son and solution check if the connector to the terminal of Loop Out or Loop In is loose Check if the circuit between Loop Out and Loop In exists an interruption Problem a fault of loop short is report...

Страница 24: ...int MCP Fire Hydrant Call Point HydrCP Sounder Visual Indicator Sounder Strobe SoundStro Sounder Sounder Visual Alarm Strobe Strobe Alarm Bell Alarmbell Conventional Optical Detector ConvOptD Conventi...

Страница 25: ...DelugeVal Generator Generator Stabilized Pressure Pump PressPump Fire Pump FirePump Foam Pump FoamPump Water Pump WaterPump Air Conditioner Air con Fire Emergence Evacuation Broadcast BCST Fire Emerg...

Страница 26: ...SEC1000 FIRE ALARM CONTROL PANEL...

Отзывы: