Operation manual for JTF-GDM-936E spot-type multisensor

smoke and heat detector

Before installation and use of the product, please read the product operation manual

carefully

I.

General

JTF-GDM-936E spot-type composite smoke-sensing and temperature-sensing fire detector (hereinafter
referred to as the detector) is a multi-element composite detector constituted jointly by a smoke sensor
and a semiconductor temperature sensor in respect of technological structure and circuit structure. It has
not only the performance of photoelectric smoke-sensing fire detectors but also the performance of
temperature-sensing fire detectors.
This detector uses a non-polarity two-wire bus system, and can be jointly used with the 9000 series
alarm controllers produced by our company.

I

I. Features

1.

Electronic encoding, to offer simple and reliable engineering adjustment;

2.

Non-polarity two-wire bus;

3.

Key device self-diagnosis function;

4.

Shift compensation function and contamination report function for dust accumulation.

III. Technical indices

1.

Operating voltage: 24 V (pulse modulation)

2.

Operating current: Monitoring current ≤ 0.5 mA; alarm current ≤ 1.5 mA

3.

Sensing technology: Double-sensing technology containing photoelectric sensor and temperature
sensor with temperature sensing type: A2

4.

Encoding mode: Electronic encoding with encoding range 1-324

5.

Wiring mode: Non-polarity two-wire system

6.

Indicator lamp: Red, flashing once per 12 seconds for polling, and constantly on for alarm

7.

Installation height: ≤ 8 m

8.

Protected area: For the specific protected area, see relevant provisions in the China national
standard GB 50116 Code for design of automatic fire alarm systems

9.

Operating environment: Temperature: -10 °C - +50 °C; relative humidity: ≤ 95%, non-condensing

10. Outside dimensions: Diameter: 100 mm; height: 55 mm (with base)
11. Weight: About 100 g
12. Housing material: ABS
13. Standards followed: GB 4715-2005, GB 4716-2005

IV. Appearance and outside dimensions of product (as shown in Fig. 1)

Fig. 1

2

V. Product use and engineering application

1.

Schematic diagram for installation of matched base, as shown in Fig. 2:

Fig. 2

2.

Wiring mode: The detector is connected into a compatible fire alarm controller via a two-wire bus

system through non-polarity connection mode and the L1 and L2 of the two-wire bus system are
connected with the terminals 1 and 3 of the matched base. The schematic diagram for connection of
multiple detectors and a controller is shown in Fig. 3.

Fig. 3

3.

Address encoding: As shown in Fig. 4, connect the detector through a detector base on the encoder

with L1 and L2 connected in non-polarity mode; set the encoder to encoding function, compile a correct
address code, and press the “Run” key to complete the address encoding setup.
(Note: For the detailed operations, please refer to the encoder operation manual.)

Fig. 4

Terminal definitions (Non-polarity
two-wire system):
1 - Signal terminal (L1)
2 - No pin
3 - Signal terminal (L2)
4 - No pin

Intelligent

two-wire

bus

controller