Operation manual for JTF-GDM-936E spot-type multisensor
smoke and heat detector
Before installation and use of the product, please read the product operation manual
carefully
I.
General
JTF-GDM-936E spot-type composite smoke-sensing and temperature-sensing fire detector (hereinafter
referred to as the detector) is a multi-element composite detector constituted jointly by a smoke sensor
and a semiconductor temperature sensor in respect of technological structure and circuit structure. It has
not only the performance of photoelectric smoke-sensing fire detectors but also the performance of
temperature-sensing fire detectors.
This detector uses a non-polarity two-wire bus system, and can be jointly used with the 9000 series
alarm controllers produced by our company.
I
I. Features
1.
Electronic encoding, to offer simple and reliable engineering adjustment;
2.
Non-polarity two-wire bus;
3.
Key device self-diagnosis function;
4.
Shift compensation function and contamination report function for dust accumulation.
III. Technical indices
1.
Operating voltage: 24 V (pulse modulation)
2.
Operating current: Monitoring current ≤ 0.5 mA; alarm current ≤ 1.5 mA
3.
Sensing technology: Double-sensing technology containing photoelectric sensor and temperature
sensor with temperature sensing type: A2
4.
Encoding mode: Electronic encoding with encoding range 1-324
5.
Wiring mode: Non-polarity two-wire system
6.
Indicator lamp: Red, flashing once per 12 seconds for polling, and constantly on for alarm
7.
Installation height: ≤ 8 m
8.
Protected area: For the specific protected area, see relevant provisions in the China national
standard GB 50116 Code for design of automatic fire alarm systems
9.
Operating environment: Temperature: -10 °C - +50 °C; relative humidity: ≤ 95%, non-condensing
10. Outside dimensions: Diameter: 100 mm; height: 55 mm (with base)
11. Weight: About 100 g
12. Housing material: ABS
13. Standards followed: GB 4715-2005, GB 4716-2005
IV. Appearance and outside dimensions of product (as shown in Fig. 1)
Fig. 1
2
V. Product use and engineering application
1.
Schematic diagram for installation of matched base, as shown in Fig. 2:
Fig. 2
2.
Wiring mode: The detector is connected into a compatible fire alarm controller via a two-wire bus
system through non-polarity connection mode and the L1 and L2 of the two-wire bus system are
connected with the terminals 1 and 3 of the matched base. The schematic diagram for connection of
multiple detectors and a controller is shown in Fig. 3.
Fig. 3
3.
Address encoding: As shown in Fig. 4, connect the detector through a detector base on the encoder
with L1 and L2 connected in non-polarity mode; set the encoder to encoding function, compile a correct
address code, and press the “Run” key to complete the address encoding setup.
(Note: For the detailed operations, please refer to the encoder operation manual.)
Fig. 4
Terminal definitions (Non-polarity
two-wire system):
1 - Signal terminal (L1)
2 - No pin
3 - Signal terminal (L2)
4 - No pin
Intelligent
two-wire
bus
controller