Merlin RS Installation & Operation Manual

 

 

REV 06                                                                                                                                                                                     Page 10 of 12

 

TECHNICAL SPECIFICATION 

 

Mechanical 

Mounting 

Wall Mounted  

Entry 

1/2

 12.5mm DIA Rear Entry 

Size (W x H x D) 

86 x 114 x 35mm (Low Profile RS - 86 x 114 x 25mm) 

Weight (Max) 

0.164Kg max 

Enclosure 

ABS UL Flame retardant 

 IP40 

Electrical 

24V AC/DC Power Rating 

12-24VDC (11-32 VDC) / 24VAC, (20-27 VAC) 50-60Hz 

230VAC Power Rating 

Nominal 230VAC, (90-250V AC), 50-60Hz 

Internal Fuse 

Resettable PPTC 240VAC, 400mA 

Communication 

127 units max 

Power Consumption Max 

5W Max 

Environmental 

Operating Temperature 

-10 to 50°C  

Storage  

10-30°C / 0 to 95% RH 

Humidity 

0 to 95% RH (continuous) non-condensing. 

Atmospheric Pressure 

80 to 110Pa 

Altitude 

<2000m 

Installation Cat (230V Voltage) 

II (Class 2) Pollution Degree 2 

Installation Cat (24V Voltage) 

III (Class 3) Pollution Degree 2 

I/Os 

Analog Outputs 

3x Linear 0-10V/2-10V CO2, Temperature & Humidity. 
Thermistor (10K3) 

Digital Networks 

BACnet MS/TP / MODBUS RTU (Parity: None Data bit: 8bit Stop bit: 1) 

Relay Outputs 

1x SPST 70mA  

Thermistor 

Betatherm 10K3A1B

  

For alternative Thermistors, contact your supplier 

Cable Spec 

Power 

1.0 

 2.5mm

2

 max 

Analog Output 

1.0 

 2.5mm

2

 max 

Digital Output 

1.0 

 2.5 mm

2

 

twisted pair + ground, shielded cable with 120Ω 

characteristic impedance. 

Relays 

1.0 

 2.5mm

2

 max 

User Interface 

Language 

English 

Optional Display 

2.8” TFT 

 

Optional LED Indication 

Green: Power (OK)  
Yellow: Warning (Pre-Alarm)  
Red: Danger (Alarm)  

Conformance 

Safety  

BS 61010-1 (CE / UKCA) 

Electromagnetic Compatibility 

BS 50270 (CE / UKCA) 

Other (Applied or Considered) 

IGEM/UP/11 
BS 50543  

Sensing

 

CO2 

(ppm)

 

Temperature 

(°C)

 

Humidity 

(%RH)

 

Sampling: Diffusion Type NDIR 
Indication Range: 400 

 5000ppm 

Response: t90 <120s 
Calibration: ABC Logic Self Calibration - 
Warm Up Time: ~1 Minute 
Accuracy: 5% FS @ 25°C 
Lifespan: >5 Years 
Resolution: 1ppm 

Fully Calibrated 
Normal Indication Range: 0-50°C 
Response: t63% @ 25°C ~20s Typical 
Excellent long term stability 
Strong anti-interference 
Warm Up Time: ~1 minute 
Accuracy: ±0.5° @ 10-45°C 
Resolution: 0.1° 

Fully Calibrated 
Indication Range: 0-100% RH 
Quick Response: t63% @ 25°C ~8s 
Excellent long term stability 
Strong anti-interference 
Warm Up Time: ~1 minute 
Accuracy: ±2% @ 15-30°C (20-90%RH) 
Resolution: 0.1% 

 

 

 

Содержание Merlin RS Series

Страница 1: ...com Merlin RS Series Safety Health Monitoring Room Sensors INSTALLATION OPERATION Please read these instructions carefully before use and retain for future reference These instructions can also be dow...

Страница 2: ...Information 4 Coverage 4 Positioning 4 Mounting Instructions 5 PCB Overview 5 Power Wiring 6 10V Output Wiring 6 VFC Relay Wiring 7 Thermistor Wiring 7 RS 485 Wiring 7 Analog Configuration Switches 8...

Страница 3: ...in material and workmanship for a period of 3 Years from the date of purchase The manufacturer s liability hereunder is limited to replacement of the product with repaired product at the discretion of...

Страница 4: ...knowledge of CO2 dispersion process plant systems and any equipment involved Seek advice where necessary in consultation with both safety and electrical engineering personnel Consider air flow pattern...

Страница 5: ...mm 1 2 cut out Execute the mounting and connections NOTE Terminals are pluggable type for ease 4 Secure the front cover by aligning the top and then securing the M2 screw in place PCB Overview All Cla...

Страница 6: ...inear output for CO2 PPM Temperature C F and Humidity rH During normal operation the output of the device is proportional to the values In normal operation output levels are proportional to the gas le...

Страница 7: ...configured in a single bus topology connecting multiple buses in parallel or branching multiple units from the main bus may introduce impedance mismatches reflections and or signal distortions Ensure...

Страница 8: ...Output Linear Scale ON 2 10V OFF 0 10V OFF 0 10V B1 NOT USED B2 NOT USED The average concentration of CO2 in air is around 400ppm or 0 4 TH Temperature and Humidity Digital RS 485 Configuration Switch...

Страница 9: ...e a valid reading output There are no warnings alarms for Temperature or Humidity levels CO2 warning levels will depend on configuration at install PPM Parts Per Million CO2 Range OK Low CO2 Warning H...

Страница 10: ...utputs 1x SPST 70mA Thermistor Betatherm 10K3A1B For alternative Thermistors contact your supplier Cable Spec Power 1 0 2 5mm2 max Analog Output 1 0 2 5mm2 max Digital Output 1 0 2 5 mm2 twisted pair...

Страница 11: ...Merlin RS Installation Operation Manual REV 06 Page 11 of 12 Page intentionally left blank...

Страница 12: ...ort is made to ensure the accuracy of this document however S S Northern can assume no responsibility for any errors or omissions in this document or their consequences S S Northern would greatly appr...

Отзывы: