Circuit Board Terminals 

 

2.1

 

Power 

A 100-240VAC mains electrical supply should be supplied to 

the panel. This should be externally fused at 3 Amps 
connected to the terminal detailed [POWER IN].

 

 

 

2.2

 

Gas Valve Output 

This is a 100-240VAC power output for connections to a gas 
solenoid valve detailed on the board [TO VALVE]. 
 
 
 
2.3

 

Building Management System (BMS)  

 

Connections to Building Management systems.  
This is a relay that changes state in alarm or when gas is on/off and other 

external relays that affect other devices and controls such as purge fans, 
audible alarms etc. 

 
Detailed on the circuit board as [TO BMS] normally closed (N/C), common 

(COM) and normally open (N/O). These are volt free connections.  
 

 
2.4

 

Remote Emergency Buttons 

 

The terminal for remote emergency shut-off buttons is detailed on the circuit 
board as [EM REM].  
These connections are linked out as a factory setting.  
 
Remote emergency shut-off buttons should be volt free and wired to the 
CT1250. 

 

 

 
2.5

 

Supply and Extract Fan PD Switches 

 

These terminals are used to receive an input signal from external air 

pressure switches or external current monitors.  

These are linked out as a factory setting as shown.  
 
Wiring to switches & current monitors should be made using two-core 

volt free connections.  

 
If only one fan is being used the terminals not in use should be left linked 

out. 

Содержание Merlin CT1250

Страница 1: ...Merlin CT1250 User Guide Rev 08 07 19 1 Merlin CT1250 Ventilation Interlock System with Current Monitoring User Guide Please read this guide carefully and retain for future use...

Страница 2: ...4 Remote Emergency Buttons 4 2 5 Supply and Extract Fan PD Switches 4 2 6 Fan current monitoring 5 2 7 Potentiometers 5 2 8 Service Mode Switch 5 3 Operation 6 3 1 System ON and OFF 6 3 2 Emergency Sh...

Страница 3: ...ard The PCB should be removed before drilling entry holes into the case Important Warning Statements Never ignore your device when in alarm This device requires a continual supply of electrical power...

Страница 4: ...fans audible alarms etc Detailed on the circuit board as TO BMS normally closed N C common COM and normally open N O These are volt free connections 2 4 Remote Emergency Buttons The terminal for remot...

Страница 5: ...SENS2 Potentiometer The fan s should be run at the minimum required speed and the relevant potentiometer turned slowly clockwise until the green LED on the circuit board lights up This indicates the...

Страница 6: ...ke or break a circuit on gas on gas off valve open or valve closed This will tell the BMS whether or not the kitchen has use of the gas supply 3 4 Fire Alarm Integration The Merlin CT1250 can be integ...

Страница 7: ...running Extract Fan Under normal working the LED will illuminate GREEN If a supply fan fault is present the LED will be flashing If the LED flashes for more than 20 seconds the gas will be shut off ON...

Страница 8: ...Merlin CT1250 User Guide Rev 08 07 19 8 5 Troubleshooting...

Страница 9: ...e any accumulated dust from the outer enclosure once a month NEVER use detergents or solvents to clean your device this may permenantly or temporarily damage the panel NEVER spray air fresheners hair...

Страница 10: ...Merlin CT1250 User Guide Rev 08 07 19 10...

Страница 11: ...Merlin CT1250 User Guide Rev 08 07 19 11...

Страница 12: ...liable for loss of use of this product or for any indirect special incidental or consequential damages or costs or expenses incurred by the consumer or any other user of this product whether due to a...

Отзывы: