S&S Northern Merlin 1000VW+ Скачать руководство пользователя страница 5

Merlin 

 

  

 

 

 

 

 

 

Product Data Sheet 

 

 

 

 

S&S Northern Ltd

  

5  

 

Gas on LED 

 When the gas service touch button has been activated the Merlin  will check the 

installation for gas leaks. If gas proving is successful, the gas valve will open and the green 
‘Gas On’  LED will illuminate.

 

 GREEN = Gas On 

 OFF = Gas Off 

 

  Electric on LED 

                 When the electric service touch button has been activated, the electrical supply is turned on   

               and the Electric LED will illuminate BLUE. 

   

      

   

 

  BLUE = Electric On 

    

  FLASHING = Electric Off, Electric button enabled 

                 OFF = Electric Off, Electric button disabled 

 

  Water on LED 

  

  When water service touch button has been activated, the water supply is turned on and the  

               Water LED will illuminate BLUE.  

  

  BLUE = Water On  

  

  FLASHING = Water Off, Water button enabled  

  

  OFF = Water Off, Water button disabled  

 

  Testing LED 

 This LED will illuminate GREEN for approximately 30 seconds when the panel is  

 

checking the integrity of the gas installation upon start up. 

 GREEN = proving the gas line, do NOT operate any appliances. 

 

Test Fail LED 

 Under normal working conditions this LED is off. When the panel detects a gas leak on start-

up or incorrect wiring at the gas pressure transmitter the LED will illuminate AMBER and the 
gas valve will remain closed. 

OFF = OK 
AMBER = gas proving failed 

 

Pressure Low LED  

 Under normal working conditions the LED is off. The LED will illuminate AMBER when 

pressure of the gas supply drops below 12mBar for 10 secs. The gas valve will close. (The 
system will only go to pressure low from gas on). 

 OFF = OK  
 AMBER = gas supply pressure low.  

 

   Timeout LED 

 

   Under normal working conditions this LED is off. This LED will illuminate AMBER when     

 

   auto-shut down has occurred. 

  

   OFF = OK 

    

   AMBER = auto-shut down 

 

EM Stop LED  

If an emergency shut off button (either remote or on the panel) is pressed, the LED will 

illuminate AMBER and the gas will be turned off. The EM Stop button must be re-set before 
restarting the system. 

OFF = OK  

AMBER = EM Stop button pressed  

 

Содержание Merlin 1000VW+

Страница 1: ...Merlin 1000VW Product Data Sheet S S Northern Ltd 1 Gas Safety Products Merlin 1000VW Gas Proving Electric Water Isolation System Installation operating and maintenance 20 01 2017...

Страница 2: ...as Detected 4 2 11 FS 123 4 2 12 Fan PD Switch 4 2 13 12v DC 4 2 14 Internal Buzzer 4 3 Operation Instructions 4 3 1 How to turn the system on and off 4 3 2 Explanation of LED status 4 Power LED 4 Gas...

Страница 3: ...ally fused at 3 Amps 2 4 Electric Contactor An electrical output will be supplied to an electrical contactor supplied by others This will be internally fused at 3 Amps and should be connected to the t...

Страница 4: ...the fans when the control panel is switched on 2 12 Fan PD Switch This terminal is used to receive an input signal from external air pressure switches or external current monitors This terminal is li...

Страница 5: ...panel is checking the integrity of the gas installation upon start up GREEN proving the gas line do NOT operate any appliances Test Fail LED Under normal working conditions this LED is off When the p...

Страница 6: ...MS integration The Merlin 1000VW can be integrated with a BMS to make or break a circuit on gas on gas off valve open or valve closed This will tell the BMS whether or not the room has use of the gas...

Страница 7: ...acia of the Merlin 1000VW labelled Fill Time and Prove Time They are factory set in the off position Fill and prove time can be changed by turning the relevant dip switch to on position Fill time Off...

Страница 8: ...ns and Fire Alarm input wired in series purchased separately VOLT FREE INPUT 10 Methane CO or LPG Detector power supply and volt free input purchased separately CO2 Monitor purchased separately VOLT F...

Страница 9: ...ww snsnorthern com info snsnorthern com South East Division Tel 44 0 1702 291 725 Fax 44 0 1702 299 148 south snsnorthern com Rev Date Author Description 01 20 01 2017 S S Northern BT Merlin 1000VW Pr...

Отзывы: