Merlin 1000BH 

 

 

 

                                                                User Guide 

 

Rev: 08   08-19

 

 

1  

 

 

 

Merlin 1000BH 

Gas proving and detection system 

 

 

 

 

 

 

 

 

User Guide 

Please read this guide carefully and retain for future use. 

 

Merlin 1000BH 

 

 

 

                                                                User Guide 

 

Rev: 08   08-19

 

 

2  

 
 

 

 

Table of contents 

 

1

 

General Information

 .......................................................................................... 3

 

2

 

Circuit Board Terminals

 ..................................................................................... 4

 

2.1

 

POWER

 ........................................................................................................................... 4

 

2.2

 

GAS VALVE

 .................................................................................................................... 4

 

2.3

 

GAS DETECTOR 1 & 2

 .................................................................................................... 4

 

2.4

 

PRESSURE SENSOR

 ......................................................................................................... 4

 

2.5

 

EM REMOTE

 .................................................................................................................... 5

 

2.6

 

BMS OUT

 ......................................................................................................................... 5

 

2.7

 

FIRE PANEL

 ..................................................................................................................... 5

 

2.8

 

TEMP SENSOR

 ................................................................................................................. 5

 

2.9

 

12VDC

 ............................................................................................................................ 5

 

3

 

Operation & Setup Guidance

........................................................................... 6

 

3.1

 

How to turn the system on and off

 ............................................................................. 6

 

3.2

 

Using the Emergency Shut Off

 .................................................................................... 6

 

3.3

 

Building Management System Connection

 .............................................................. 6

 

3.4

 

Gas Fill and Prove Time

 ................................................................................................ 6

 

3.5

 

Auto Reset

 ..................................................................................................................... 7

 

4

 

Panel LED Status

 ................................................................................................. 7

 

5

 

Maintenance

 ..................................................................................................... 8

 

6

 

1000BH Wiring Spec

........................................................................................... 9

 

7

 

Manufacturer’s Warranty

 ................................................................................ 12

 

 

  

 

 
 

 

 

 

 

 

 

 

 

 

 
 

 

Merlin 1000BH 

 

 

 

                                                                User Guide 

 

Rev: 08   08-19

 

 

3  

1

 

General Information  

 

The Merlin 1000BH is a gas pressure proving & gas detection panel for use in various 
applications. 
The system comprises a control panel and a gas pressure sensor. The Merlin 1000BH can     
receive connections from remote emergency shut-off buttons, two gas detectors, fire panel 
and heat detector. It also can be integrated with a BMS.  
 
The information contained within this guide should be referenced for typical installation and 
operation only. For site specific requirements that may deviate from the information in this 
guide – contact your supplier.  
 
1.1

 

Panel Mounting  

The control panel is designed for surface mounting using 4 mounting screws. Removing the 
cover on the panel gives access to the circuit board, this should be removed before drilling 
entry holes into the case. 
 
 
 

 

Important Warning Statements 

 

 

 

It is recommended that this device be commissioned upon installation and serviced annually. 

 

Do not apply lighter gas or other aerosols to gas detectors – this will cause extreme damage. 

 

Never ignore your device when in alarm. 

 

This device requires a continual supply of electrical power – it will not work without power. 

 

This device should not be used to substitute proper installation, use and/or maintenance of fuel burning 

appliances including appropriate ventilation and exhaust systems. 

 

Your product should reach you in perfect condition, if you suspect it is damaged, contact your supplier. 

 

 
 
 
 
 
 
 
 
 

Information on waste disposal for consumers of electrical & electronic equipment. (EEE) 

When this product has reached the end of its life it must be treated as Waste Electrical & Electronics Equipment 

(WEEE). Any WEEE marked products must not be mixed with general household waste, but kept separate for 

the treatment, recovery and recycling of the materials used.  

 

Please contact your supplier or local authority for details of recycling schemes in your area. 

 

Merlin 1000BH 

 

 

 

                                                                User Guide 

 

Rev: 08   08-19

 

 

4  

2

 

Circuit Board Terminals 

 

2.1

 

POWER  

A 100-240VAC electrical supply should be externally fused 
at 3 Amps and be connected to the terminals marked 
[LNE POWER] 
 
2.2

 

GAS VALVE  

A gas solenoid valve should be powered using the 
terminals marked [LNE GAS VALVE].  
 
 
 
 
2.3

 

GAS DETECTOR 1 & 2 

The terminals detailed on the circuit board as [GAS DETECTOR 1] and [GAS DETECTOR 2].  
 
These connections are [+ -] and [

] these can be 

wired to a Merlin gas detector. Natural gas, Carbon 
monoxide or LPG.  
 
 
Please refer to the detector manual for more 
information. If no detector is being used leave the link 
in. Other detector types are available. 
 

 

 

2.4

 

PRESSURE SENSOR 

The terminals marked [+ - IN]. 
 
These wire to the gas pressure sensor which is screwed into the downstream 
port on the gas solenoid valve.              

             

 
 
 

 

 
Min Operating Pressure = 12Mbar 
Max Operating Pressure = 100Mbar 
 
 
 

 
ENSURE THIS IS WIRED AS PICTURED & SCREWED TO THE DOWNSTREAM PORT OF THE GAS SOLENOID VALVE

 

  

 

Merlin 1000BH 

 

 

 

                                                                User Guide 

 

Rev: 08   08-19

 

 

5  

 

2.5

 

EM REMOTE  

The terminal for remote emergency shut-off buttons is marked as [EM REMOTE].  
 
These connections are linked out as a factory setting. 
Remote emergency shut-off buttons should be volt free. 
 

 

 

2.6

 

BMS OUT 

Terminals are available on the circuit board for connections to Building 
Management systems.  
 
This is a relay that changes state in alarm or when gas is on/off and can be 
used in conjunction with the [12VDC] output and other external relays that 
affect other devices and controls such as purge fans, audible alarms etc. 
 
Marked on the circuit board as [BMS OUT] Normally Closed (N/C),  
Common (COM) Normally Open (N/O).  
These are volt free connections.  

 

 

2.7

 

FIRE PANEL 

The terminal for fire alarms is detailed on the circuit board as [FIRE PANEL].  
 
These connections are linked out as a factory setting.  
Fire alarms should be volt free and wired to the Merlin 1000BH using two-core 

cable.  

 

 

2.8

 

TEMP SENSOR

 

The terminal for heat detectors is detailed on the circuit board as [TEMP 
SENSOR].  
 
These connections are linked out as a factory setting.  
 
Heat detectors should be volt free and wired to the Merlin 1000BH using 
two-core cable. 

 

 
2.9

 

12VDC  

This is a permanent 12v DC output when there is power at the panel.  
 
This is normally used to power a PM2 current monitor. (Supplied separately)  

Merlin 1000BH 

 

 

 

                                                                User Guide 

 

Rev: 08   08-19

 

 

6  

3

 

Operation & Setup Guidance 

 

3.1

 

How to turn the system on and off 

Turn the key switch to ON position. 
Turn the key switch to OFF position or remove power.  

 

3.2

 

Using the Emergency Shut Off 

 

The Emergency shut off button is located on the front of the panel.  
There is also a facility for remote shut off buttons to be wired in series.  
 
The Emergency shut off button(s) will cut off the gas supply when activated.  
To reinstate the system, the Emergency shut off button(s) will need to be reset and the panel 
restarted.  

 

3.3

 

Building Management System Connection 

The Merlin 1000BH can be integrated with a BMS to make or break a 
circuit on gas on/gas off, (valve open or valve closed). This will tell the 
BMS whether or not electrical power is being sent to the solenoid. 
 
There is a dip-switch located on the inside facia of the Merlin 1000BH 
labelled [BMS SEL].  
 
This is factory set in the ‘OFF’ position which signals the BMS on gas 
on/gas off. When switched to the ‘ON’ position, the 1000BH will only 
signal the BMS on a fault, i.e. gas detected, EM Stop pressed, etc.  
 
 

3.4

 

Gas Fill and Prove Time 

Gas fill and prove times are adjustable. There are two dip-switches located on the inside facia 
of the Merlin 2000S labelled “Fill Time” and “Prove Time”. They are factory set in the ‘off’ 
position.  
Fill and prove time can be changed by turning the relevant dip switch to on position.  

 

 
FILL TIME is the amount of time the gas valve is open to fill the gas line. 
Off
 – 5 seconds 
On – 10 seconds  
 

PROVE TIME is the amount of time the system tests the gas line for any leaks. 

Off – 30 seconds                                                                                                                                        
On – 50 seconds  

 

 

Once the settings has been changed please remove power for 10 seconds.  

 

Merlin 1000BH 

 

 

 

                                                                User Guide 

 

Rev: 08   08-19

 

 

7  

3.5

 

Auto Reset 

The Merlin 1000BH has a built-in auto reset feature.  
 
There is a dip-switch located on the inside facia of the Merlin 1000BH 
labelled [Auto Reset]. This is factory set in the ‘OFF’ position.  
When the power is restored after the power cut, the panel has to be 
restarted manually.  
 
On installation, this can be switched to the ‘ON’ position if required.  
This will instruct the system to restart automatically when power is 
restored after the power cut.

 

 

 

4

 

Panel LED Status 

 

 
When the system is connected to the mains supply, the red dot of the S&S logo located in the 
bottom right corner of the panel will illuminate.  
 

 

Gas on  

When the key switch is turned on, the Merlin 1000BH will check the installation for gas leaks.  
If gas proving is successful, the gas valve will open and the green ‘Gas On’ LED will illuminate.

  

ON = Gas On  
OFF = Gas Off  
 

 

Testing  

This LED will illuminate GREEN for approximately 30 seconds when the panel is checking the 
integrity of the gas installation upon start up.  
GREEN = proving the gas line, do NOT operate any appliances  
 

 

Test Fail  

Under normal working conditions this LED is off. When the panel detects a gas leak on start-up, 
the LED will illuminate AMBER. Gas valve will remain closed.  
OFF = OK  
ON = gas proving failed  

Merlin 1000BH 

 

 

 

                                                                User Guide 

 

Rev: 08   08-19

 

 

8  

 

Pressure Low 

Under normal working conditions the LED is off. The LED will illuminate AMBER when pressure of 
the gas supply drops below 12mBar for 10 secs. The gas valve will close.  
OFF = OK  
ON = gas supply pressure low.  
 

 

Gas Detector 1/ Gas Detector 2  

Under normal working conditions this LED is off. If the external Merlin detector connected 
detects gas this will show RED and the Gas valve will turn off. 
OFF = OK  
ON = Gas detected.  
 

 

Heat Detector 

 Under normal working conditions this LED is off. If the temperature of the boilers reaches 72 
Degrees Celsius or higher (Heat detector required), the LED will show AMBER and the Gas valve 
will turn off.  
OFF = OK  
ON = High temperature detected (72 Degrees Celsius or higher) 
 

 

EM Stop  

If an emergency shut off button (either remote or on the panel) is pressed, the LED will 
illuminate AMBER and the gas will be turned off. The EM Stop button must be re-set before 
restarting the system. 
OFF = OK  
ON = EM Stop button pressed. 

 

 

Fire Alarm Panel 

If a fire alarm panel has been triggered, the LED will illuminate Amber and the gas will be 
turned off. The Fire alarm panel must be re-set before restarting the system. 
Off = OK 
ON = Fire alarm panel triggered. 
 

 

5

 

Maintenance 

 

To keep your panel in good working order, you must follow these steps: 
 

 

DO carefully remove any accumulated dust from the outer enclosure once a month. 
 

 

NEVER use detergents or solvents to clean your device – this may permenantly or temporarily 
damage the panel 
 

 

NEVER spray air fresheners, hair spray, paint or other aerosols near the device. 

 

 

NEVER paint the device. Paint will seal vents and interfere with the device. 

Merlin 1000BH 

 

 

 

                                                                User Guide 

 

Rev: 08   08-19

 

 

9  

6

 

1000BH Wiring Spec  

 

 

 

1.

 

POWER: Mains supply 100-240VAC.  

2.

 

GAS VALVE: Gas Solenoid Valve Power Output, 230VAC, Max 3A.  

3.

 

GAS DETECTOR 1: 12V power supply. VOLT FREE INPUT (detectors sold separately).  

4.

 

GAS DETECTOR 2: 12V power supply. VOLT FREE INPUT (detectors sold separately 

5.

 

PRESSURE SENSOR: Red + positive / Black – negative / Blue IN. 

6.

 

EM REMOTE: Remote emergency stop buttons and Fire Alarm input wired in series 
(purchased separately). VOLT FREE INPUT  

7.

 

BMS OUT: Normally Closed, Common and Normally Open.  

8.

 

FIRE PANEL: (Supplied by others). VOLT FREE INPUT 

9.

 

TEMP SENSOR: (purchased separately). VOLT FREE INPUT 

10.

 

12VDC: Permanent 12VDC output when there is power at the panel. 

11.

 

GAS & PROVE TIME SWITCH 

12.

 

AUTO RESET & BMS SELECTION SWITCH 

 
 
 
 
 