S&P PCLPD100XHP Скачать руководство пользователя страница 1

WARNING

READ AND SAVE THESE INSTRUCTIONS

Installer: Leave this manual with the homeowner.

CAUTION

CLEANING & MAINTENANCE

OPERATION

TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, 

OBSERVE THE FOLLOWING:

Model:  PCLPD100XHP

1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.

2. This product is designed for installation in ceilings up to a 12/12 pitch (45 degree angle). Duct connector must point up.

3. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.

4. Please read specification label on product for further information and requirements.

For quiet and efficient operation, long life, and attractive appearance - lower or remove grille and vacuum interior of unit with the dust brush attachment.

The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noises, replace the motor with the 

exact service motor. The impeller should also be replaced.

VENTILATION FAN

a). Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.

b). Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to 

prevent power from being switching on accidentally. When the service disconnecting means cannot be locked, securely 

fasten a prominent warning device, such as a tag, to the service panel.

c). Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes 

and standards, including fire-rated construction codes and standards.

d). Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning 

equipment to prevent backdrafting.

Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire 

Protection Association (NFPA),and the American Society for Heating, Refrigeration and Air Conditioning Engineers 

(ASHRAE), and the local code authorities.

e). When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.

f). Ducted fans must always be vented to the outdoors.

g). Acceptable for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupter) - protected 

branch circuit (ceiling installation only).

h). This unit must be grounded.

i). Not for Use in Kitchens.

j). To reduce risk of fire and to properly exhaust air, be sure to duct air outside – Do not vent exhaust air into spaces 

within walls or ceilings or into attics,crawl spaces, or garages.

k). WARNING: To Reduce The Risk Of Fire Or Electric Shock, Do Not Use This Fan With Any Solid-State Speed Control 

Device.

l). The fan must not be installed in a ceiling thermally insulated to a value greater than R40.

Cod: 0060303007-A

Humidity sensor knob

50

 80

  100

1 2

1 2

1 2

Switch position

Duct  diameter

Airflow(CFM)

4" Oval

Low airflow knob

Control box

To change the pre-selected airflow, adjust

the control switches as per the table above.

is the position of switch

See “Connect Wiring” for details.

The control box, located inside the fan housing, has three separate adjustments:

(1) The low airflow knob adjusts the lower airflow from 30 CFM up to the air flow rate of the 

high fan speed determined by the toggle switch setting.

     The low speed is de-activated when set between OFF-30 CFM (factory set to OFF).

(2) The humidity sensor knob set user-adjustable setpoint. The humidity sensor is de-acti-

vated when set between OFF-30% (factory set to 80% (Ambient temperature of 25

)).

(3) The toggle switch will adjust the upper fan speed setting from 50 to 100 CFM. (factory 

set to 100CFM).

S

Max.

30

CFM

OFF

50%

70%

H (%)

80

45

60

OFF

30

Содержание PCLPD100XHP

Страница 1: ...g equipment to prevent backdrafting Follow the heating equipment manufacturer s guideline and safety standards such as those published by the National Fire Protection Association NFPA and the American Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE and the local code authorities e When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden...

Страница 2: ... is detected a Humidity above a user adjustable setpoint 30 80 relative humidity b rapid increases in humidity After delay timer 20 minutes returns fan to the default low speed Humidity sensor description according to HUMIDITY SENSOR OPERATION and SENSITIVITY ADJUSTMENT HUMIDITY SENSOR OPERATION The humidity sensing fan uses a sophisticated humidity sensor that responds to a rapid increases in hum...

Страница 3: ...ts the inner surface of the stud Screw the mounting flange to the stud stud through the holes A and B on the same side Screw the hanger bar onto the stud through its hole Screw the hanger bar to housing with screw A The minimum installation distance between studs is 13 3 8 in 340mm Connect the round ductwork not included to the damper duct connector and run the ductwork to a roof or wall cap not i...

Страница 4: ... the date of original purchase THERE ARE NO OTHER WARRANTIES EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF SUITABILITY FOR A PARTICULAR PURPOSE During this six year period S P will at its option repair returned products or parts or provide replacement products or parts without charge for any product or part which is found to be defective under normal use This warranty doe...

Отзывы: