Ventilation unit with heat recuperation

 

DUOVENT

®

 COMPACT RV

 

3

 

1. GENERAL

1.1 INTRODUCTION

 

This manual is intended for ventilation units with heat recuperation DUOVENT

®

 COMPACT RV. Its purpose is to provide as much information as 

possible for the safe installation, commissioning and use of this equipment. Due to the fact that our products are constantly evolving, we reserve 
the right to change this manual without prior notice.

 

1.2 WARRANTY

 

We do not guarantee the suitability of the devices for special purposes, the determination of suitability is fully in the competence of the customer 
and  the  designer.  The  warranty  for  the  devices  is  in  accordance  with  valid  legal  regulations.  The  warranty  is  only  valid  if  all  installation  and 
maintenance instructions, including protection, are observed. The warranty covers manufacturing defects, material defects or malfunctions of the 
device.

 

The warranty does not cover defects caused by:

 

 

 

 

 

 

 

 

 

 

 

 

I

mproper use and design

I

mproper handling (does not apply to mechanical damage)

D

uring transport (compensation for damage caused during transport must be claimed from the carrier)

I

ncorrect installation, incorrect electrical connection or protection

I

ncorrect operation

U

nprofessional intervention in the device

D

isassembling the device

U

se in unsuitable conditions or in an unsuitable manner

W

ear and tear caused by normal use

T

hird party intervention

D

ue to a natural disaster

When claiming the warranty, it is necessary to submit a report containing:

 

 

 

 

 

 

D

ata on the complaining company

D

ate and number of the sales document

E

xact specification of the defect

W

iring diagram and fuse details

M

easured values when starting the device

V

oltage

C

urrent

A

ir temperature

A

ir flow

 

The warranty repair is carried out in principle at the discretion of S&P UK Ventilation Systems

 Ltd

. at the company's service centre or at the 

installation site. The method of eliminating the defect is solely at the discretion of the service company S&P UK Ventilation Systems

 Ltd

. The 

complaining party will receive a written statement on the result of the complaint. In the event of an unjustified complaint, the complaining

 

party 

pays all costs of its implementation.

Warranty conditions

 

The device must be installed by a professional air handling service company. 

DUOVENT

®

 COMPACT RV, incl. control system DVAV, DCAV, 

DCOP, must be commissioned only by the Seller or by the person authorised by the Seller. Failure to comply with this condition will 
result in the termination of the Buyer's rights from defective performance and from the Quality Warranty. Detailed terms are specified i

 

the Seller's Complaint Procedure. 

The electrical connection must be made by a specialist electrical company. Installation a nd location of the 

de

vice must be unconditionally performed in accordance with ČSN 33 2000-4-42 (IEC 364-4-42). The device must be subjected to an initial 

electrical inspection according to ČSN 33 1500. 

The device must be regulated to the designed air-conditioning parameters.

 

When starting 

the device, it is necessary to measure the above-specified values and make a record of the measurement, confirmed by the company putting the 
device into operation. In the event of a complaint about the equipment, it is necessary to submit a record of the above- mentioned parameters 
from commissioning together with the declaration protocol together with the initial revision, which t he operator acquires within the commissioning 
and maintenance of the electrical installation.

 

During the operation, it is necessary to perform regular inspections of electrical equipment within the deadlines according t

o ČSN 33 1500 and 

inspection, maintenance and  cleaning of  air-conditioning equipment. It  is necessary to  keep a  "Maintenance and inspection book" for  the 
maintenance and service of the device, for which the device operator is responsible.

 

When taking over the device and unpacking it from the transport packaging, the customer is obliged to perform the following inspections. It is 
necessary to check the integrity of the device, as well as whether the delivered device exactly agrees with the ordered device. It is always 
necessary to check whether the label and identification data on the transport packaging, equipment or engine correspond to the designed and 
ordered parameters. Due to the continuous technical development of the equipment and changes in technical parameters reserved by the 
manufacturer, and the time lag between the project and the implementation of own sales, fundamental differences in the parameters of the 
equipment at the date of sale cannot be ruled out. The customer is obliged to inform the manufacturer or supplier about such changes before 
ordering the goods. Subsequent complaints cannot be taken into account

.

Содержание DUOVENT COMPACT RV Series

Страница 1: ...DUOVENT COMPACT RV Ventilation unit with heat recuperation www solerpalau co uk...

Страница 2: ...t evaporator 17 5 2 7 Connection of condensate drain 17 5 2 8 Bypass mixing flap 19 5 2 9 Inlet and outlet flap 20 5 2 10 Frequency converter of rotation exchanger 20 5 2 11 Basic accessories 22 5 2 1...

Страница 3: ...ny DUOVENT COMPACTRV incl controlsystemDVAV DCAV DCOP must be commissioned only by the Seller or by the person authorised by the Seller Failure to comply with this condition will result in the termina...

Страница 4: ...pliance by a responsible person The user must ensure that children do not play with the device Cleaning and maintenance of the appliance must not be carried out by children without supervision 2 GENER...

Страница 5: ...unit with mixing flap enabling 100 air circulation For the circulation mode the unit must be fitted with KL input flaps KL input and discharge flap with preparation for mounting the actuator filtering...

Страница 6: ...ON OF FAULT RESET BUTTON OF EL HEATER NOTICE ON LOCATION OF THE CONDENSATE DRAINAGE NECK IN THE BOTTOM OF THE UNIT NOTICE ON CONNECTION OF FAN MOTOR PROTECTIONS WARNING OF THE NECESSITY OF INSULATION...

Страница 7: ...water exchangers evaporator X E 150 B E E 20 Type A mm B mm D mm E mm L mm L for MX mm X mm Y mm DUOVENT RV 800 678 678 470 160 1306 1620 108 104 DUOVENT RV 1800 835 992 600 300 1620 1934 110 5 117 5...

Страница 8: ...include Investor details Information on the installation company or designer Detailed technical data of all components of the unit fan recuperator heater cooler filter Overall dimensions of the unit a...

Страница 9: ...5 51 resp SN 332000 5 51 ed 3 SN 332000 1 ed 2 The ambient temperature must be between 20 and 40 C The unit can transport air without solid fibrous sticky aggressive chemical and explosive additives T...

Страница 10: ...be protected during storage against mechanical damage dirt and corrosion caused by permanent condensation of water vapour on the surface of the unit During storage it is necessary to protect the units...

Страница 11: ...mmended distances from all obstacles to ensure easy maintenance and operation of the unit If the unit is fitted with Digireg or regulation system it is necessary to ensure free space from the system d...

Страница 12: ...rsonal injury The technical characteristics of this manual must not be changed The motors of the unit must not be changed The unit can be connected to the three phase electric grid with alternating vo...

Страница 13: ...age these can be removed only after the attachment of both flanges on the one hand to the unit and on the other to the air distribution systems 5 2 3 CONNECTION OF ELECTRIC HEATER The unit equipped wi...

Страница 14: ...NNECTION The unit fitted with the water heater unit code DCA or DCB is connected to the heating media by means of three way mixing unit see Types of ESU control units The water heater outlets are loca...

Страница 15: ...t exchangers the heating water pipes must not act on the necks of the heat exchangers due to their weight and expansion We recommend the antifreeze mixture as a heat transfer medium for all outdoor un...

Страница 16: ...r can then be disconnected from the cooling water distribution system and removed from the unit Max operating water pressure of water coolers 1 6 MPa Hydrogen exponent of heating water pH 7 9 Heating...

Страница 17: ...refrigerant circuit for direct cooling must be carried out by a specialist company It is mandatory to perform a Refrigerant leak test on the refrigerant circuit This test is performed only by a techn...

Страница 18: ...me of overpressure siphon type SF P 400 PR bottom edge of the condensate tray unit floor level 360 158 height of floor panel lower edge above the floor level incl anti vibration pads of thickness 5 mm...

Страница 19: ...1100 Pa Siphons are used individually for each condensate drain on the unit The condensate drain behind the individual siphons of one unit assembly can be connected to one pipe Never connect the unit...

Страница 20: ...UOVENT COMPACT RV 800 the frequency converter is located inside the rear panel in the ETA section and is accessible after opening the operator side door In DUOVENT COMPACT RV 1800 7800 the frequency c...

Страница 21: ...he frequency converter for sizes DUOVENT COMPACT RV 1800 7800 without mixing with one or two exchanger positions frequency converter Location of the frequency converter for sizes DUOVENT COMPACT RV 18...

Страница 22: ...the unit The siphon must be fitted to the unit gas tightly via the enclosed rubber sleeve Max usable vacuum 1100 Pa Overpressure siphon SF P 400 PR the siphon must be completely filled with water to p...

Страница 23: ...t must never be loaded by tension and twisting of the connected piping Mixing units should be mounted on separate hinges using heating sleeves on the wall pipes or on an auxiliary structure When place...

Страница 24: ...nspection or service activities The connection and earthing of electrical equipment must comply in particular with SN 33 2000 5 51 ed 3 SN 33 2000 5 54 ed 3 and the BP and B decrees on professional co...

Страница 25: ...onfigured temperature Regulation to a constant temperature of the exhaust air uses one temperature sensor in the exhaust pipe the supplied air is heated or cooled to the required set temperature withi...

Страница 26: ...ngs The cable routes of safe and mains voltage must be separated due to electromagnetic compatibility requirements It is necessary to build 2 cable routes at a distance of at least 20 30 cm from each...

Страница 27: ...er pressure sensor optional S8 Thermostat as protection against freezing of the direct evaporator S9 Supply fan pressure sensor mandatory monitors fan operation S10 Intake air temperature sensor S11 R...

Страница 28: ...ter cartridges Flap movability Tight connection to distribution lines Closing of all doors and service holes Any faults must be rectified before starting the unit for the first time 7 2 TRIAL OPERATIO...

Страница 29: ...ts may only be connected to the mains in accordance with the applicable regulations The device must be installed in such a way that under normal operating conditions it cannot come into contact with a...

Страница 30: ...e electric motor bearings If you need to replace the entire unit or fan open the door by opening the locks by turning 90 The fan is located on rubber silent blocks Loosen the 4 nuts lift and remove th...

Страница 31: ...ion exchanger ATTENTION TO OVALITY including the adjustment of the sealing elements 8 2 4 PERIODIC INSPECTIONS Perform periodic inspections at least once a year as part of a summer service inspection...

Страница 32: ...n the event that we find any part is defective the product will be repaired or at the company s discretion replaced without charge provided that the product has been installed in accordance with the e...

Страница 33: ...S OF FAN EC ELECTRIC MOTOR PLASTIC PARTS OF THE CONTROL SYSTEM A B C D E TRANSFORMER CONTROL BOARD SECURING ELEMENTS MAIN SWITCH GLANDS 6 FILTERS WITH PLASTIC FRAME 1 FLAP ACTUATORS a b Open the unit...

Страница 34: ...TS OF THE CONTROL SYSTEM 1 2 3 4 5 voltage transformer control board Securing elements Maim switch Glands a b c d Open the cabinet cover Disconnect cables Remove parts 1 2 3 4 5 Tools used 4 FILTERS W...

Отзывы: