background image

Ventilation unit with heat recovery

DUOVENT

®

 COMPACT DV

 

4

 

1.3 SAFETY REGULATIONS

 

Adherence to these instructions should not pose any safety, health or environmental risks in accordance with EC directives (CE marked). The 
same applies to other products used in the device or during installation. Consider the following warnings:

 

 

 

 

 

 

Observe the safety instructions to prevent damage to the device or personal injury. 
The technical information in this manual must not be changed.

 

It is forbidden to interfere with the motor of the device.

 

In order for the device to comply with EC directives, the device must be connected to the mains in accordance with the applicable regulations. 
The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving part and / or 
live part.

 

The device complies with the applicable regulations for the operation of electrical equipment. 
Always disconnect the device from the power supply before carrying out any work on it.

 

Appropriate tools must be used when handling or maintaining the device. 
The device must only be used for the purposes for which it is intended.

 

This appliance is not intended for use by children under 8 years of age and persons with reduced physical, sensory or mental capabilities, 
or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a 
responsible person. The user must ensure that children do not play with the device. Cleaning and maintenance of the appliance must not 
be carried out by children without supervision.

 

 

 

 

 

 

2. GENERAL

The DUOVENT

®

 COMPACT DV unit is manufactured in accordance with valid Czech and European laws, decrees, standards and technical 

rules. The unit may only be installed and used in accordance with this documentation. The manufacturer is not liable for damage caused by 
other uses and the buyer bears all risks. Changes and modifications to the complete product that could affect safety and proper function are 
prohibited. Installation and operating documentation must be available to the operator and service. It is advisable to place it close to the 
installed unit.

 

When disposing of the unit, the relevant environmental and waste disposal regulations must be observed. In the case of final disposal, it is 
necessary to follow the principles of separate collection. The applicable standards, safety regulations and generally accepted technical rules must 
be observed during installation, electrical connection, commissioning, repairs and maintenance of the units. Assembly of units, connection of 
electrical installation, commissioning of the unit, repairs, maintenance and operation may be performed only by a natural or legal person with a 
valid authorization. The current version of this manual is available at www.solerpalau.co.uk

 

3. TECHNICAL DATA

3.1 MANUFACTURING LABEL AND INFORMATION LABELS

 

Each unit is provided with a manufacturing label, which contains the basic data needed to identify the device. The label is usually located on the 
front of the unit or on the connection side of the heat exchanger parts.

 

Key to distinguish the variants of DUOVENT

®

 Compact DV recuperation units 

(„TYPE“ field on the label):

 

C O M P A C T

 

5

 

0

 

0

 

D C A

 

D C C

 

1

 

2

 

3

 

4

 

5

 

6

 

8

 

10

 

1 - unit size - 500, 800, 1200, 1800, 3000, 4200, 5100, 6000, 6900, 7800

 

2 - heater type:

 

DI 

- electric heater

 

DCA 

- water, temperature drop on water 80/60 °C

 

DCB - 

water, temperature drop on water 45/35 °C 

3 - water cooler type:

 

DCC 

- water for gradient on water 6/12 °C

 

DX 

- direct evaporator for refrigerant R410A, evaporating temperature 6 °C

 

(for a direct evaporator, it is always necessary to specify the type of refrigerant, the required capacity and the 
division of the refrigeration capacity into sections according to the type of condensing unit used).

 

For evaporation units used for reverse operation with the thermal pump this fact must be specified in the order.

 

DXr 

- evaporator in connection for reversible operation (cooling / heating), refrigerant R410A 

4 - 

MX 

- mixing damper with preparation for mounting the actuator

 

www.solerpalau.co.uk

 

SP

 

F

 

V

 

M

 

V

 

A

 

V

 

G

 

4

 

/

 

G

 

4

 

K

 

L

 

M

 

X

 

D

 

V

 

D

 

U

 

O

 

V

 

E

 

N

 

T

 

Содержание DUOVENT COMPACT DV

Страница 1: ...INSTRUCTION MANUAL www solerpalau co uk DUOVENT COMPACT DV Ventilation unit with heat recovery...

Страница 2: ...n Connection of electric heater Connection of water heater Connection of water cooler Connection of direct evaporator Connection of condensate drain Bypass and mixing flap Inlet and outlet flap 5 2 10...

Страница 3: ...ation Warranty conditions The device must be installed by a professional air handling service company DUOVENT COMPACTDV incl controlsystemDVAV DCAV DCOP must be commissioned only by the Seller or by t...

Страница 4: ...hat could affect safety and proper function are prohibited Installation and operating documentation must be available to the operator and service It is advisable to place it close to the installed uni...

Страница 5: ...nit for ventilation of pool halls Order examples DUOVENT COMPACT DV 3000 DI DX MX KL G4 F7 F7 DVAV JH2 Unit size 3000 with electric heater direct evaporator bypass and mixing flap two stage filtration...

Страница 6: ...INSULATION OF THE ANTIFREEZE PROTECTION CONTACT SENSOR WARNING DO NOT OPERATE THE UNIT WHILE CONSTRUCTION WORK IN PROGRESS AIR FLOW CALCULATION PLATE LOCATED AT FAN SUCTION PRESSURE ORIFICE PORT WARNI...

Страница 7: ...0 182 DUOVENT DV 1200 521 992 312 80 2091 260 5 260 5 582 300 500 DUOVENT COMPACT DV 500 to 1200 under ceiling arrangement positions xH AH unit position drawn UNIT BOTTOM VIEW Exchanger outlets UNIT T...

Страница 8: ...2 X3 L Y D Y Exchanger outlets D 20 D 1 2 1 2 DETAIL OF CONNECTING FLANGE INTEGRATED IN WALL PANEL 19 18 18 18 Condensate drains 152 152 152 21 www solerpalau co uk 40 A 150 B A B 150 F 157 42 42 X1 X...

Страница 9: ...94 694 694 627 627 694 694 694 694 694 1085 1085 1085 1085 1085 1085 1085 DUOVENT COMPACT DV 1800 to 7800 floor arrangement positions xP AP unit position drawn X3 X1 X2 X E E X 1 2 1 2 19 18 18 18 Tra...

Страница 10: ...00V 50Hz 3000 1238 927 1 8 1 4 89 1 3500 320 387 3000 DCA DCC 3000 DCA DX 21 8 21 8 21 3 21 3000 DI 15 22 4200 4200 DCA 4200 DCB 4200 DCA DCC 4200 DCA DX 4200 DI 29 8 22 30 2 20 5 29 8 3 400V 50Hz 420...

Страница 11: ...ES EXCHANGER OUTLETS ETC Ensure proper balancing of the transported unit The ropes above the unit must be stretched to prevent damage The outdoor variants of the units are fitted with transport profil...

Страница 12: ...is necessary to check the insulation of the HVAC piping in parts with a risk of condensation Condensate formed in the air duct can in unfavourable conditions spill into the interior of the unit where...

Страница 13: ...tion box 5 1 2 HOW TO STORE THE UNIT AT THE DESTINATION The unit is designed for floor mounting in a vertical position positions marked xV in the unit code or horizontal position positions marked xP i...

Страница 14: ...applicable regulations The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving or live part DUOVENT COMPACT DV units comply with...

Страница 15: ...let and outlet ports with respect to the position of the exchanger connection pipes Neck variants vertical arrangement viewed from unit operation side INLET OUTLET OUTLET INLET OUTLET OUTLET INLET INL...

Страница 16: ...TLET OUTLET www solerpalau co uk INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET...

Страница 17: ...INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET...

Страница 18: ...n it is exceeded the operating thermostat opens and switches off the heater after cooling below 60 C the heater automatically switches on again Location of the release button under the cover on the un...

Страница 19: ...nger connections it is necessary for example to hold the heat exchanger neck with a second wrench so that the tightening torque is not transmitted to the heat exchanger body Table of dimensions of wat...

Страница 20: ...n screws on the heat exchanger collectors The heat exchanger can then be disconnected from the heating water distribution system and removed from the unit Max operating water temperature of water heat...

Страница 21: ...the cooler must be vented after connecting and filling the system with cooling water The vent screws are located directly at the heat exchanger connection necks The vent screws are accessible either...

Страница 22: ...specialist company It is mandatory to perform a Refrigerant leak test on the refrigerant circuit This test is performed only by a technician with the appropriate authorization according to the law 5 2...

Страница 23: ...ING FLAP In the basic version each unit is equipped with a bypass flap of the plate heat exchanger BP The bypass is used for summer ventilation defrost control of the recuperation exchanger in the eve...

Страница 24: ...on mode Location of mixing and bypass flap for DUOVENT 500 800 1200 units with MX mixing mode www solerpalau co uk ETA flap Mixing flap MX ODA flap Bypass flap BP Circulation flap C part 1 ODA flap Ci...

Страница 25: ...uators 5 2 10 BASIC ACCESSORIES 5 2 10 1 CONDENSATE DRAIN TRAPS Condensate traps must be ordered as a separate item as they are not included with the unit Vacuum type siphon scheme SF P 300 bottom edg...

Страница 26: ...ected piping Mixing units should be mounted on separate hinges using heating sleeves on the wall pipes or on an auxiliary structure When placed under the ceiling it is necessary to maintain control an...

Страница 27: ...I C control system to the electrical distribution network is made by a separate supply cable which is not part of the delivery of the device www solerpalau co uk Ventilation unit with heat recovery DU...

Страница 28: ...ts according to the set parameters in the automatic summer winter mode according to the outdoor temperature and time dependencies Manual mode selection is also possible The heater can be hot water con...

Страница 29: ...otation of the fans the correct phasing of the damper actuators and mixing valves If the unit is equipped with a Digireg control system directly from the factory a SETPACK test package has been perfor...

Страница 30: ...onnection to distribution lines Closing of all doors and service holes Any faults must be rectified before starting the unit for the first time 7 2 TRIAL OPERATION The material content of the comprehe...

Страница 31: ...applicable regulations The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving or live part DUOVENT COMPACT DV units comply with t...

Страница 32: ...NH IH2 JH2 MH2 NH2 263 295 263 365 KH LH OH PH KH2 LH2 OH2 PH2 263 295 263 295 1200 1200 all positions 420 365 365 420 ETA filter size ETA mm ODA filter size ETA mm Size of DUOVENT DV Vnom m3 h Neck...

Страница 33: ...replace the entire unit or fan open the door by opening the locks by turning 90 The fan is located on rubber silent blocks Loosen the 4 nuts lift and remove the fan as shown in the following figure K...

Страница 34: ...nitor the implementation of the measures taken Check the siphons for condensate drainage especially their permeability and tightness especially the tightness of the mounting on the unit and the tightn...

Страница 35: ...l applicable standards and national and local building standards IF CLAIMING UNDER WARRANTY Please return the completed product carriage paid to your local authorised distributor All returns must be a...

Отзывы: