SAMWON ENG CO.,LTD SU-105 Controller User Manual Page
1/3
Automatic Temperature Controller SU-105 User Manual
Model
Temperature range
Output
SU-105 IP
IC
(-50.0℃~150℃)
Main/Aux(DC12V)
Main/Aux(Relay)
※ Thank you for purchasing a SamWon ENG CO.,LTD
product. This manual contains the information on how
to use the product. Keep it in a safe place and refer to it
whenever necessary.
Display Unit
Displays a current temperature or user-set
temperature
Main/Aux Output
Indicates the main or auxiliary output is
ON or OFF
Set key
Up key
Down key
Setting button
Increment button
Decrement button
▶
Power controller for heaters and coolers
Hysteresis 0.0~9.9 degree C., 0~240 second delay timer, Normal/Reverse selection.
▶
Contains a digital timer to control defrosting. Range: 1~999 minute.
▶
User configuration control
˚
You can specify a valid temperature range that a user is allowed to use.
˚
You can prevent a user from changing the setting of hysteresis, delay time,
and normal/reverse.
▶
Turn on the power and wait until the current
temperature appears on the display.
▶
Press set key once and notice
the display unit blinks.
▶
Use Up or Dn key to change the setting.
If you hold down a key for longer than
4 seconds, the number will increase or
decrease rapidly.
Note: The selectable range might be
limited by User configuration control.
▶
Store the setting in memory by pressing
set key for longer than 5 seconds.
▶
The unit show the current temperature
and start working.
▶
The main output uses terminal 7 ~ 9.
Note: For information on Auxiliary
output (Alarm/Timer), refer to Section
13. How to set Alarm Output.
①
How to connect sensors
▶
When connecting sensors, use the
following figure. If you connect the
lines incorrectly or a different type
of sensors, the display unit will
show ‘
Err
’.
②
Sensor line extension
▶
A Pt100 sensor line can be extended
up to 100 M.
▶
An IC/Humidity sensor line can be
extended up to 500 M.
▶
You MUST use a shielded line to prevent
the noise when extending a line.
③
Sensor input correction (when current temperature is incorrect)
▶
Press set key for longer than 5 seconds, when the display unit shows a current
temperature
▶
Release the key when you see
diF
. Select
rSt
by pressing set key.
▶
Select a correction temperature using Up or Dn key.
▶
Store the setting in memory by pressing the set key for longer than 5 seconds.
For example,
Current
temperature
rSt
corrected
temperature
Displayed
current
temperature
20.0 ℃
+
+
-5.0 ℃
=
=
15.0 ℃
20.0 ℃
10.0 ℃
30.0 ℃
Voltage
AC220V (50/60Hz) ±10% (AC110V,option)
Power
5VA or less
Input Sensor
K(CA) with a load/line of 100Ω or less
PT100Ω with a load/line of 5Ω or less
Accuracy
K(CA):display the value ±0.5% +1digit
Pt100:display the value ±0.2% +1digit
Hysteresis
0.1℃ ~ 9.9℃
Control output
Relay Output:AC250V 5A
Relay life time:300,000 or grater
Control operation
ON/OFF Control
Setting Methode
Digital Methode with Up or Down key
Etc.
Sensor input correction,Delay timer,Normal/Reverse selection,Defrosting Timer
Environment Temperature 0℃ ~ 50℃
Environment humidity
85% RH or less
1. Description of display
set
up
dn
2.Capability and applications of the product
3.How to set main output
<Main Output Terminal>
Coil
Magnet
메인
전원
작동
기계
AC
220V
Pow
er
Mac
hine
<Display Current>
①Red/White ②Shield/Black
4. How to connect sensors
①White②Black③Black
5.External dimension
70
34
76
28
PANEL CUT OUT
70
(unit: mm)
6.Product specification
<Rear panel terminal>
Sensor
Aux output
Main output
Power
B
W
sh
RELAY
3A
RELAY
3A
AC
220V
R/W
B
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩
⑪
A B B
’
RTD
+ -
TC
Sensor
Aux output
Main output
Power
B
W
sh
RELAY
3A
RELAY
3A
AC
220V
R,W
B
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩
⑪
up
dn
set
on
℃
Up key
Set key
Display Unit
Down Key
Main Output
IC/HUM
Ca-K