36
Water Flow rate
Section
Water Flow Rate (LPM)
8HP
10HP
12HP
20HP
30HP
Standard
condition
80
96
114
190
285
Operation range
48~96
58~115
68~137
114~228
170~342
80
70
60
50
40
30
20
10
0
80
70
60
50
40
30
20
10
0
0
50.0
100.0
150.0
Water Flow rate of cooling water (L/min)
Pr
es
sur
e Dr
op
fr
om plat
e
ty
pe heat
ex
changer
(kP
a)
AM080MXWA
∗
AM100MXWA
∗
AM120MXWA
∗
90
80
70
60
50
40
30
20
10
0
90
80
70
60
50
40
30
20
10
0
0
100
50
200
150
250
Water Flow rate of cooling water (L/min)
Pr
es
sur
e Dr
op
fr
om plat
e
ty
pe heat
ex
changer
(kP
a)
AM200MXWA
∗∗
Water Flow rate of cooling water (L/min)
Pr
es
sur
e Dr
op
fr
om plat
e
ty
pe heat
ex
changer
(kP
a)
80
70
60
50
40
30
20
10
0
0
200
100
300
400
80
70
60
50
40
30
20
10
0
AM300KXWA
∗∗
NOTE
•
When the water flow rate is out of the operation range, stop the outdoor unit and take care of the cause
before restarting the operation. (Allowable range: 60~120% of the standard water flow rate)
•
For the piping work, set the pump capacity considering the pressure drop of the plate heat exchanger to maintain a
proper flow rate.