SERVICE

Manual

CONTENTS

AIR CONDITIONER

1. Product Specifications

2. Operating Instructions

3. Disassembly and Reassembly

4. Refrigerating Cycle Diagram

5. Set Up the Model Option

6. Troubleshooting

7. Exploded Views and Parts List

8. Block Diagram

9. PCB Diagram

10. Wiring Diagram

11. Schematic Diagram

ROOM AIR CONDITIONER

 DB98_16202A(4)_co  04/3/29 12:10 PM  Page 3

Содержание UQ07P2GE

Страница 1: ...09P2GE UQ12P4GE UQT12P4GB UQT12P4GE SERVICE Manual CONTENTS AIR CONDITIONER 1 Product Specifications 2 Operating Instructions 3 Disassembly and Reassembly 4 Refrigerating Cycle Diagram 5 Set Up the Model Option 6 Troubleshooting 7 Exploded Views and Parts List 8 Block Diagram 9 PCB Diagram 10 Wiring Diagram 11 Schematic Diagram ROOM AIR CONDITIONER DB98_16202A 4 _co 04 3 29 12 10 PM Page 3 ...

Страница 2: ... 24 3 65 1 220 240 50 680 630 3 0 2 8 98 6 97 8 21 0 250V 10 16A 795x258x179 660x495x235 31 3x10 2x7 0 26 0x19 5x9 3 7 5 22 5 ø6 35 x 5 ø9 52 x 5 ø18 x 2 000 Rotary Cross flow Propeller steel steel 11 25 2ROW 10STEP 1ROW 18STEP CAPILLARY TUBE 290 680 MRA99137 9201 Size Power Perfor mance Wall mounted 2 60kW 8 990 BTU h 2 90kW 8 990 BTU h 1 4 7 0 24 40 51 2 89 3 41 1 220 240 50 900 850 4 0 3 8 97 8...

Страница 3: ...240 50 730 680 3 3 3 1 96 2 95 4 21 0 250V 10 16A 795x258x179 660x495x235 31 3x10 2x7 0 26 0x19 5x9 3 7 5 26 0 ø6 35 x 5 ø9 52 x 5 ø18 x 2 000 Rotary Cross Flow Propeller steel steel 15 25 2ROW 10STEP 1ROW 18STEP CAPILLARY TUBE 360 630 RAC12144 9622 Size Power Perfor mance Wall mounted 2 65kW 8 990BTU h 2 90kW 8 990BTU h 1 4 7 0 24 39 51 2 82 3 30 1 220 240 50 940 880 4 3 4 0 95 0 95 7 21 0 250V 1...

Страница 4: ...1 220 240 50 730 680 3 3 3 1 96 2 95 4 21 0 250V 10 16A 795x258x179 660x495x235 31 3x10 2x7 0 26 0x19 5x9 3 7 5 26 0 ø6 35 x 5 ø9 52 x 5 ø18 x 2 000 Rotary Cross Flow Propeller steel steel 15 25 2ROW 10STEP 1ROW 18STEP CAPILLARY TUBE 360 630 RAC12144 9622 Size Power Perfor mance Wall mounted 9 000 10 000 1 4 7 0 24 39 51 9 57 11 4 1 220 240 50 940 880 4 3 4 0 95 0 95 7 21 0 250V 10 16A 795x258x179...

Страница 5: ...Condition Maximum Operation Condition Indoor unit Outdoor unit Indoor unit Outdoor unit Wall mounted 12 000 13 000 10 500 1 9 8 2 2 4 43 53 10 0 10 5 7 44 1 220 60 1 200 1 240 1 410 5 5 5 7 6 5 99 2 98 9 98 6 32 0 250V 10 16A 890x285x179 720x530x260 35 0x11 2x7 0 28 3x20 9x10 2 8 5 33 0 ø6 35 x 5 ø12 7 x 5 ø18 x 2 000 Rotary Cross Flow Propeller steel steel 15 25 2ROW 12STEP 2ROW 24STEP CAPILLARY ...

Страница 6: ...emp C 20 25 30 35 40 45 32 4 24 0 30 6 22 5 28 8 21 0 27 0 19 0 24 0 17 0 21 5 15 0 6 5 5 5 4 5 3 5 9K BTU Outdoor inlet air D B temp C Low pressure kg cm 2 G Indoor inlet air D B temp C 20 25 30 35 40 45 32 4 24 0 30 6 22 5 28 8 21 0 27 0 19 0 24 0 17 0 21 5 15 0 6 5 5 5 4 5 3 5 12K BTU Outdoor inlet air D B temp C Low pressure kg cm 2 G Indoor inlet air D B temp C DB98_16202A 4 _1 04 3 29 12 16 ...

Страница 7: ...perature by the pressing the temperature button On Off UP DOWN Low Medium High Automatic rotated Sleep button The sleep timer can be used when you are cooling or heating your room to switch the air conditioner off automatically after a period of 6 hours Turbo button The air conditioner cools or heats the room as quickly as possible After 30minutes the air conditioner is reset automatically to the ...

Страница 8: ...ime display FUNCTION OF KEY Anion button Press the button to generate ion from the air conditioner NAMED OF KEY No 9 10 11 12 13 On Timer button The On Timer enables you to switch on the air conditioner automatically after a given period of time that is from 30 minutes to 24 hours To set the operating time press the button one or more times until the required time display Timer Set Cancel button A...

Страница 9: ... Prevention against freeze 5 TURBO MODE This mode is available in AUTO COOL HEAT DRY FAN MODE When this button is pressed at first the air conditioner is operated powerful state for 30 minutes regardless of the set temperature room temperature When this button is pressed again or when the operating time is 30 minutes turbo operation mode is canceled and returned to the previous mode But if you pre...

Страница 10: ...ou can set the period of time from 30 minutes to 24 hours 11 GENERATING ANION The air conditioner can generate anion with an ionizer in the indoor unit 12 SELF DIAGNOSIS 13 BUZZER SOUND Whenever the On Off button is pressed or whenever change occurs to the condition which is set up or select the compulsory operation mode buzzer is sounded beep Indoor unit room temperature sensor error open or shor...

Страница 11: ...tion 2 2 1 Replace PCB model option No Yes Remove power cord Replace the PCB module Check the connection and plug in Refer to set up the Model option 17 19page Replace another PCB Does all display lamp blink DB98_16202A 4 _1 04 3 29 12 17 PM Page 10 ...

Страница 12: ... Panel upper 3 Slide the lower Front Grille down then disassemble it by pulling it forwards 4 Open the upper Front Grille by pulling right and left sides of the Grille 5 Take the left and right Filter out 6 Loosen one of the right screw and detach the Terminal Cover 7 Detach the thermistor from the Front Grille 8 Loosen 5 fixing screws of Front Grille 9 Pull the lower left and right of discharge s...

Страница 13: ...e thumb to remove the hook And press the right of the upper side of the Panel Grille with the fingers And then disassemble the Panel Grille 1 Take all the connector of PCB upper side out Including Power Cord 2 Detach the outdoor unit connection wire from the Terminal Block 3 If pulling the main PCB up it will be taken out 1 Pull Tray Drain out from the Back Body DB98_16202A 4 _1 04 3 29 12 17 PM P...

Страница 14: ...tion Pipe 3 Detach the Holder Pipe at the rear side 4 Loosen 3 fixing screws of right and left side 5 Detach the Heat Exchanger from the indoor unit 1 Loosen 2 fixing screws and separate the Motor Holder 2 Loosen 1 fixing screw of Fan Motor with a M3 wrench 3 Detach the Fan Motor from the Fan 4 Detach the Fan from the left Holder Bearing DB98_16202A 4 _1 04 3 29 12 17 PM Page 13 ...

Страница 15: ... the Cover Terminal 2 Loosen 1 fixing screw and detach the Cover Control 3 Detach the connection wire from the Terminal Block 4 Loosen 13 fixing screws and detach the Cabinet Front 5 Loosen 1 fixing screw of Ass y E part 6 Loosen 4 fixing screws and detach the Cabinet Side DB98_16202A 4 _1 04 3 29 12 17 PM Page 14 ...

Страница 16: ...osen 5 fixing screws and detach the Motor Bracket from the Base 1 Loosen 2 fixing screws of left and right side 2 Disassemble the inlet and outlet pipe by welding 3 Detach the Heat Exchanger 1 Open the Terminal Cover of Compressor and unscrew the Connection Terminal 2 Disassemble the inlet and outlet pipe of Compressor by welding 3 Loosen 3 bolts of the lower part 4 Detach the Compressor DB98_1620...

Страница 17: ... Unit Outdoor Unit T1 T2 2 Way valve 3 Way valve Gas side Heat Exchanger Evaporator Heat Exchanger Condenser Liquid side Capillary tube 4 Way valve Cooling Heating Gas leak check point Compressor Cross fan Propeller fan DB98_16202A 4 _1 04 3 29 12 17 PM Page 16 ...

Страница 18: ...play panel reads or repeatedly Setting is not required if you must a value which has a default Push the button to set the display panel to Every time you push the button the display panel reads repeatedly 3 Push the button to set the display panel to Every time you push the button the display panel reads repeatedly 4 Push the button to set the display panel to Every time you push the button the di...

Страница 19: ... part to and check the display part The display part shows Press the Mode Selection key to set the display part to and check the display part The display part shows Step 4 Pressing the ON OFF button When pressing the operation ON OFF key with the direction of remote controller for unit the sound Ding or Diriring is heard and the OPERATION ICON lamp of the display is flickering at the same time the...

Страница 20: ...G10 SEG11 SEG12 SH07ZP2 SH07ZP2A AQ07P2GE SH09ZP2 SH09ZP2A SH12ZP4 SH12ZP4A AQ12P4GE AQ09P2GE AQT12P4GB AQT12P4GE 0 2 4 5 6 7 1 7 0 2 1 d 0 2 5 2 6 6 1 7 0 3 4 0 0 6 6 0 6 5 1 7 0 3 6 2 0 6 6 0 6 6 1 7 0 3 6 2 0 2 5 3 6 5 1 7 0 3 4 0 0 6 7 0 E 6 1 7 0 3 6 2 0 6 8 0 E 6 1 7 0 3 5 1 DB98_16202A 4 _1 04 3 29 12 20 PM Page 19 ...

Страница 21: ...ndoor fan stop intermittently in HEAT mode In case of heat pump model Indoor fan and outdoor fan stop operation intermittently in a HEAT mode 1 2 3 4 5 6 7 8 9 Operation of air conditioner Explanation It indicates power is on The LED stops blinking if the opera tion ON OFF button on the remote control unit is pushed In happens after a delay of 3 minutes when the compressor is reoperated The same p...

Страница 22: ...ing Lamp off No response from the remote control operation signal Unable to operate the outdoor unit Plug out and plug in 5 seconds later Press the TURBO button with the remote control In 3 minutes check the voltage between the indoor unit terminal block N 1 and 1 Able to operate the remote control Unable to operate the remote control AC198V AC242V No power source displayed OK Press the ON OFF but...

Страница 23: ...eck whether two wires of power cord are connected correctly to the terminal block and control board Check whether the fuse on the control board is normal FUSE 3 15 A 250 V Check the output of SMPS on the control board Input power AC230 15 V IC02 Input DC 12 V IC02 output DC 5 V Check the setting temperature Check the indoor unit control board Check the display board Reconnect wires correctly Repla...

Страница 24: ...r and measure the sensor resistance with an ohmmeter tester Connect the sensor to CN43 supply power and measure the voltage of 1 and 2 of the CN43 connector MICOM Error or Connector CN43 check Is the sensor resistance value 10KΩ 3 at the room temperature of 25 C Yes Poor ASS Y PCB Replace Below 0 5V Yes Poor ASS Y PCB Replace Over 4 9V Indoor unit room temperature sensor error open or short Descri...

Страница 25: ...om pipe sensor to PCB plug in and check the voltage of connector 3 and 4 If the resistance is below 0 5V or over 4 9V replace the indoor Main PCB short or disconnected in the PCB board Temperature C 15 20 25 Temperature C 30 35 40 Resistance Value Kohm 8 31 6 94 5 83 Resistance Value Kohm 14 68 12 09 10 Others The data tolerance is 3 6 2 3 Room Pipe sensor failure Indoor unit heat exchanger temper...

Страница 26: ...PERATION lamp blink Does the Solid State Relay SS71 work properly Is the supply voltage of the fan motor sufficient Test rod location PCB CN72 Condition About AC 180V Normal voltage pin 3 and 5 Fan operating Yes Yes Yes Yes No No No Check as in the procedure NO power PCB is out of order PCB should be replaced Replace Motor Fan Capacitor Fan motor should be replaced Fan motor is out of order Motor ...

Страница 27: ...should be reconnected within 5 seconds Does the OPERATION lamp blink Yes No Yes No No No Yes Yes Outdoor unit is out of order Power relay is out of order Power relay should be replaced PCB should be checked Micom is out of order Sensor Should be replaced Room temperature sensor is out of order Check as in the procedure No Power Is the room sensor normal resistor 10 C 20 C 30 C 17 96kΩ 12 09kΩ 8 3k...

Страница 28: ...tton of the remote control unit pushed Voltage at pin 57 60 of micom IC04 change Squarewave Voltage at pin 2 5 of CN61 motor connector change Squarewave UP DOWN louver motor is faulty Driver IC06 08 ULN2003A is faulty Micom IC04 is faulty Normal Check as in the procedure No Power After training on the heating operation should start in 5 minutes Is the number 38 of Micom IC04 DC 5 0V Is the number ...

Страница 29: ...o 3 and No 2 of the main PCB CN91 while operating the remote control When the voltage descends below 3V the assembly module PCB is normal and the main PCB is poor Then replace the main PCB 3 Replace the assembly display PCB because the module PCB is poor if the voltage between No 2 3 of CN91 maintains 5V after the remote control starts operation DB98_16202A 4 _1 04 3 29 12 20 PM Page 28 ...

Страница 30: ...MEMO 29 Samsung Electronics DB98_16202A 4 _1 04 3 29 12 20 PM Page 29 ...

Страница 31: ... 1 1 4 1 1 5 1 1 6 15 1 4 1 3 1 2 1 1 1 1 1 7 10 7 3 7 5 7 1 8 7 2 7 4 9 13 1 5 14 12 3 3 1 3 2 EUROPE AFRICA You can search for the updated part code number through the ITSELF URL http itself sec samsung co kr 7 Exploded Views and Parts List 7 1 Indoor Unit DB98_16202A 4 _1 04 3 29 12 20 PM Page 30 ...

Страница 32: ...R TERMINAL HIPS 1 1 DB63 00588A COVER TERMINAL HIPS 1 1 1 1 6 DB93 02530G ASS Y REMOCON ASS Y 1 1 1 1 1 1 7 DB94 00488C ASS Y BACK BODY ASS Y 1 1 DB94 00486C ASS Y BACK BODY ASS Y 1 1 1 1 7 1 DB61 01098A BACK BODY HIPS 1 1 DB61 01119A BACK BODY HIPS 1 1 1 1 7 2 DB91 00248A ASS Y ELECTRIC IONS ASS Y 1 1 1 1 1 1 7 3 DB63 00580A COVER IONIZER HIPS 1 1 1 1 1 1 7 4 DB93 01451C ASS Y CONNECTOR WIRE IONI...

Страница 33: ...95 00367E ASS Y FILTER BIO ASS Y 1 1 1 1 1 1 5 DB63 00581A COVER TERMINAL HIPS 1 1 DB63 00588A COVER TERMINAL HIPS 1 1 1 1 6 DB93 02530G ASS Y REMOCON ASS Y 1 1 1 DB93 02530J ASS Y REMOCON ASS Y 1 1 1 7 DB94 00488C ASS Y BACK BODY ASS Y 1 DB94 00488A ASS Y BACK BODY ASS Y 1 DB94 00486C ASS Y BACK BODY ASS Y 1 1 DB94 00486A ASS Y BACK BODY ASS Y 1 1 7 1 DB61 01098A BACK BODY HIPS 1 1 DB61 01119A BA...

Страница 34: ...S Y 1 5 DB63 00581A COVER TERMINAL HIPS 1 6 DB93 02531B ASS Y REMOCON ASS Y 1 7 DB94 00488C ASS Y BACK BODY ASS Y 1 7 1 DB61 01098A BACK BODY HIPS 1 7 2 DB91 00248A ASS Y ELECTRIC IONS ASS Y 1 7 3 DB63 00580A COVER IONIZER HIPS 1 7 4 DB93 01451C ASS Y CONNECTOR WIRE IONIZER ASS Y 1 7 5 DB94 00258A ASS Y BEARING ASS Y 1 8 DB94 00040R ASS Y CROSS FAN ASS Y 1 9 DB31 00152B MOTOR FAN IN 220 240V 50 60...

Страница 35: ...Samsung Electronics 34 7 2 Outdoor Unit 12 15 1 15 2 24 14 5 15 6 18 19 9 2 11 22 10 21 15 5 20 4 7 6 23 8 3 1 16 17 15 7 15 3 15 15 4 13 DB98_16202A 4 _1 04 3 29 12 20 PM Page 34 ...

Страница 36: ...0uF 450VAC 1 1 2501 001234 CAPACITOR COMP 20uF 450VAC 1 2501 001238 CAPACITOR COMP 40uF 450VAC 1 15 2 2301 001375 CAPACITOR MOTOR 1 5uF 450VAC 1 1 1 1 15 3 DB65 40049E TERMINAL BLOCK 4P 1 1 1 1 15 4 DB93 01547B ASS Y LEAD WIRE ASS Y 1 1 DB93 01547D ASS Y LEAD WIRE ASS Y 1 1 15 5 DB35 00026D OLP MRA98776 1 DB35 00026C OLP MRA99137 9201 1 DB35 00020A OLP RAC12144 9622 1 DB35 00020G OLP RAC12110 9622...

Страница 37: ...35uF 450VAC 1 1 1 2501 001236 CAPACITOR COMP 30uF 450VAC 1 15 2 2301 001375 CAPACITOR MOTOR 1 5uF 450VAC 1 1 1 1 15 3 DB65 40049E TERMINAL BLOCK 4P 1 1 1 1 15 4 DB93 01547B ASS Y LEAD WIRE ASS Y 1 DB93 01547E ASS Y LEAD WIRE ASS Y 1 1 DB93 01547D ASS Y LEAD WIRE ASS Y 1 15 5 OLP INTERNAL 1 DB35 00028G OLP RBC12107 12500 1 DB35 00028F OLP RBC12050 12500 1 DB35 00015H OLP RAC12074 9622 1 15 6 DB67 6...

Страница 38: ...MEMO 37 Samsung Electronics DB98_16202A 4 _1 04 3 29 12 20 PM Page 37 ...

Страница 39: ...Samsung Electronics 38 7 3 Ass y Control In Indoor Unit AQ0 P2G SH0 ZP2 NO PLUG DB93 02542A AQ0 P2G SH0 ZP2 PLUG DB93 02542B Ionizer DB93 02542C Titanium Filter DB98_16202A 4 _1 04 3 29 12 20 PM Page 38 ...

Страница 40: ...B ASS Y TERMINAL BLOCK PLATE TERMINAL LOW HOLDER WIRE CRAMP ASS Y THERMISTOR SCREW MACHINE SCREW MACHINE C W MODULE C W STEP MOTOR UP DOWN SEAL SCREW MACHINE C W STEPPING MOTOR C W ION PCB HOLDER DISPLAY HALF MIRROR ASS Y PCB HVPS ASS Y C W HVPS 12V SEAL POWER CORD POWER CORD SCREW MACHINE ABS ASS Y ASS Y ASS Y ASS Y SGCC M T1 2 HIPS ASS Y PH M3xL22 TH M4xL16 ASS Y ASS Y 61x40x3 30FOAM PE GRAY PH ...

Страница 41: ...Samsung Electronics 40 Exploded Views and Parts List AQ T 12P4G SH12ZP4 DB93 02541A Ionizer AQ T 12P4G SH12ZP4 DB93 02541B Titanium Filter DB98_16202A 4 _1 04 3 29 12 20 PM Page 40 ...

Страница 42: ...S Y MODULE PCB ASS Y TERMINAL BLOCK PLATE TERMINAL LOW HOLDER WIRE CRAMP ASS Y THERMISTOR SCREW MACHINE SCREW MACHINE C W MODULE C W STEP MOTOR UP DOWN SEAL SCREW MACHINE C W STEPPING MOTOR C W ION PCB HOLDER DISPLAY HALF MIRROR ASS Y PCB HVPS ASS Y C W HVPS 12V SEAL ABS ASS Y ASS Y ASS Y ASS Y SGCC M T1 2 HIPS ASS Y PH M3xL22 TH M4xL16 ASS Y ASS Y 61x40x3 30FOAM PE GRAY PH M4x10 ASS Y AUTO GRILLE...

Страница 43: ... AUTO COOL DRY FAN FAN SPEED SELECT H M L BLADE H MOVING SELECT ON OFF TIMER SELECT FUNCTION SELECT TEMPERATURE SELECT ZERO VOLTAGE DETECT BLADE CONTROL AUTO GRILLE CONTROL INDOOR FAN MOTOR CONTROL COMPRESSOR CONTROL TEMPERATURE CONTROL TIMER BUZZER CONTROL FUNCTION CONTROL TRIGGER SIGNAL SSR COMPRESSOR DRIVE OUTDOOR FAN MOTOR DRIVE STEPPING MOTOR DRIVE BUZZER DRIVE FUNCTION DRIVE COMPRESSOR CONTR...

Страница 44: ...43 Samsung Electronics 9 PCB Diagram 9 1 ASS Y MAIN PCB 7K 9K 12K 9 1 1 DB93 02685A Ionizer 9 1 1 DB93 02685L Titanium Filter TOP DB98_16202A 4 _1 04 3 29 12 21 PM Page 43 ...

Страница 45: ...Samsung Electronics 44 PCB Diagram BOTTOM DB98_16202A 4 _1 04 3 29 12 21 PM Page 44 ...

Страница 46: ...X 3P 1R 2mm STRAIGHT SN 1 SNA CN82 CONNECTOR HEADER SMW200 03 RED BOX 3P 1R 2mm STRAIGHT SN 1 SNA CN94 CONNECTOR HEADER SMW200 14 NTR BOX 14P 1R 2mm STRAIGHT SN 1 SNA CR71 C FILM MPPF 1 2uF 10 450Vac BK 38x18x30 3 1 SNA D101 DIODE RECTIFIER UG2D 200V 2A DO 204AC TP 1 SNA F701 FUSE CARTRIDGE 250V 3 15A TIME LAG GLASS 5x20mm 521 3150 401 1 SNA F701 FUSE CLIP AFC 520 1 SNA FT71 NOISE FILTER LS404190M...

Страница 47: ...06 R909 R CHIP 4 7Kohm 5 1 10W TP 2012 2 SNA R609 R CHIP 560ohm 5 1 10W TP 2012 1 SNA RY71 RELAY POWER UKH 12S 12VDC 0 9W 20000mA SPST 20mS 10mS 1 SNA RY72 73 RELAY POWER DC12V 3A 250VAC 10mS 10mS 1 SNA SS71 SSR AQG22212 12Vdc 2A 1mS 1mS 1 SNA ST11 TRANS SWITCHING JT1916 09 310V FERRITE EI1916 1 SNA VA71 VARISTOR INR14D561K RS 560V 2500A 17 5x7 5mm TP 1 SNA X501 RESONATOR CERAMIC 10MHz 0 5 TP 10 0...

Страница 48: ...368G Parts List No 1 ASS Y LED MODULE 1 SNA 2 PCB DISPLAY FR 1 T1 6 1 SNA 3 TACT SWITCH KPT 1105A 1 SNA 4 RESISTOR 200ohm 2W 2 SNA 5 RESISTOR 100ohm 2W 3 SNA 6 CONNECTOR WIRE 14P 1 SNA Specification Description Remark Q TY DB98_16202A 4 _1 04 3 29 12 21 PM Page 47 ...

Страница 49: ...OR HEADER BOX 3P 1R 2mm ANGLE SN 1 SNA 3 C CERAMIC MLC AXIAL 1nF 10 50V Y5P TP 1 9 x 3 5 1 SNA 4 DIODE SWITCHING 1N4148 100V 200mA DO 35 TP 1 SNA 5 C CERAMIC MLC AXIAL 100nF 80 20 50V Y5V TP 3 5 x 1 1 SNA 6 MODULE FRP4021H7 1 SNA Specification Description Remark Q TY DB98_16202A 4 _1 04 3 29 12 21 PM Page 48 ...

Страница 50: ...49 Samsung Electronics 10 Wiring Diagram 10 1 Indoor Unit 7K 9K 12K This Document can not be used without Samsung s authorization Code No DB98 15136A DB98_16202A 4 _1 04 3 29 12 21 PM Page 49 ...

Страница 51: ...thorization SH07ZP2X SH09ZP2X UQT12P4GB UQT12P4GE Code No DB98 15123A C1 MOTOR CAPACITOR FM FAN MOTOR C2 COMP CAPACITOR O L P OVER LOAD PROTECTOR SH12ZP4X Code No DB98 16523A C1 MOTOR CAPACITOR FM FAN MOTOR C2 COMP CAPACITOR O L P OVER LOAD PROTECTOR DB98_16202A 4 _1 04 3 29 12 21 PM Page 50 ...

Страница 52: ...X SH09ZP2AX SH12ZP4AX UQ07P2GE UQ09P2GE UQ12P4GE Code No DB68 01624A C1 MOTOR CAPACITOR FM FAN MOTOR C2 COMP CAPACITOR O L P OVER LOAD PROTECTOR This Document can not be used without Samsung s authorization DB98_16202A 4 _1 04 3 29 12 21 PM Page 51 ...

Страница 53: ...Samsung Electronics 52 11 Schematic Diagram 11 1 Indoor Unit 7K 9K 12K This Document can not be used without Samsung s authorization DB98_16202A 4 _1 04 3 29 12 21 PM Page 52 ...

Страница 54: ...y of Samsung Electronics Co Ltd Any unauthorized use of Manual can be punished under applicable International and or domestic law Samsung Electronics Co Ltd Apr 2004 Printed in Korea Code No DB98 16202A 4 DB98_16202A 4 _co 04 3 29 12 10 PM Page 2 ...