E-
17
ENGLISH
Between Indoor and Outdoor Connection Cord Specifications
Power Supply (Single Phase)
Earth Cable Communication Cable Home server
Power Supply
Max/Min(V) Connection Wire
208-230V~/60Hz
±
10%
1.25mm
2
Ø 1.6mm,1 wire
0.75~1.25mm
2
2 wires
0.75~1.25mm
2
2 wires
Adjusting air flow
E. S. P(External Static Pressure) setting for phase control motor
With its phase control motor, you can adjust the indoor unit fan speed depending on the installation condition.
If the external static pressure is high so that the duct becomes longer or if the external static pressure is low so that the
duct becomes shorter, adjust the fan speed by referring the following table. Refer to the page 18 to set the option code.
Note
represents E. S. P(External Static Pressure) range of factory setting.
You don’t have to adjust the fan speed separately if the external static pressure of the installation
place is in
. When it is out of
, input the appropriate option code.
If you input the inappropriate option code, error may occur or the air conditioner is out of order.
The option code must be inputted correctly by the installation specialist or service agent.
Static Pressure
DH140CAV
DH105CAV
Option Code
Option Code
12mmAq
016774-13C2FF-200001-300000
015774-11C2DD-200001-300000
10mmAq
016774-13C2CC-200001-300000
015774-11C28A-200001-300000
8mmAq
016774-13C2AA-200001-300000
015774-11C248-200001-300000
6mmAq
016774-13C286-200001-300000
015774-11C224-200001-300000
4mmAq
016774-13C264-200001-300000
015774-11C0F1-200001-300000
2mmAq
016774-13C240-200001-300000
015774-11C0E0-200001-300000
0mmAq
016773-13C32E-200001-300000
015773-11C1CE-200001-300000