Features and Specifications
2-24
Wired remote controller installation
5) Reassemble the Wired Remote Controller.
NOTE
• Align the controller with the upper groove first, and then insert it by turning it downwards as shown in the figure.
After assembly, check and confirm that no wires are stuck in the gap between the back and front covers.
6) Remove the front protective film.
• When installing a Wired Remote Controller by using a cable longer than 10 m (32.80 ft), you must install the communication
cable and the power cable separately. (Electrical interference can cause the Wired Remote Controller to malfunction.)
• When installing your Wired Remote Controller on the wall, consider the size of the wire hole, and select a wire with a
proper thickness.
• Wire that is connectable to Wired Remote Controller PCB.
- If you install the Wired Remote Controller by reclaiming, install it according to U-terminal cable specification.
- If you install the Wired Remote Controller by using two pieces of PVC wire, remove the 30 cm (12 inch) of the sheath
of the cable and install it only with the two pieces of wires. (Recommended specification: AWG20) SOL.
• The following are the specs of the compression ring terminal connected to your Wired Remote Controller PCB.
Range of
Permitted Wires
Rated
Size
Stud
Size
Basic Size [mm (inch)]
AWG
mm²
(inch²)
mm²
(inch²)
mm
(inch)
t
ØD
G
E
F
W
L
22~16
0.25~1.65
(0.0003 ~
0.0025)
1.5
(0.0023)
3
(0.1181)
0.7
(0.0275)
3.8
(0.1496)
10.0
(0.3937)
4.5
(0.1771)
6.5
(0.2559)
6.0
(0.2362)
21.2
(0.8346)
※ Maximum distance for connecting communication and power cable : 100 m (328 ft)
• Screws on the PCB terminal must be tightened with less than 6N-cm tightening torque. If the tightening torque is
greater, it may damage the screw thread.