19
English
19
Se
rvic
e Mode
Main
menu
Sub
menu
Function
Data
bit
Factory
setting
Description
Unit
2
1
Software code
1~6
-
Software code
-
2
Software version
1~6
-
Software version
-
3
1
Indoor unit room temperature
1,2,3
-
Room temperature
°C
2
Indoor unit EVA IN temperature
1,2,3
-
EVA IN temperature
°C
3
Indoor unit EVA OUT temperature
1,2,3
-
EVA OUT temperature
°C
4
Indoor unit EEV step
1,2,3
-
EEV step
-
5
Indoor unit option checking
(1)
Use of central control
1
-
0 – No use, 1 - Use
-
Use of drain pump
2
-
0 – No use, 1 - Use
-
Use of electric heater
3
-
0 – No use, 1 - Use
-
Use of hot water coil
4
-
0 – No use, 1 - Use
-
6
Indoor unit option checking
(2)
Use of external control
1
-
0 – No use, 1 - Use
-
Use of RPM compensation
2
-
0 – No use, 1 - Use
-
Filter time
3
-
0 – 2000 hours, 1 – 1000 hours
-
Heating temperature
compensation
4
-
0 – No use(2°C), 1 – Use(5°C)
-
EEV stop step in heating
5
-
0 – 1/80 steps, 1 – 80
-
4
1
Indoor unit main address checking
1,2
-
Main address (0~63)
-
Indoor unit main address setting
3,4
-
Main address (0~63)
(outdoor unit reset is needed to
set)
Indoor unit RMC address setting/checking
5,6
-
RMC address (00H~2FH)
-
2
Indoor unit option code setting/checking
1)*
-
Indoor unit option code
-
3
Indoor unit option switch setting/checking
1)*
-
Indoor unit option code
-
5
1
AHU setting/checking
AHU RPM setting/checking 3,4
-
0~31
1RPM
AHU humidity setting/
checking
6
2
0-30,1-40,2-50
-
2
AHU discharge
temperature setting/
checking
Use of discharge
temperature control
1
0
0-No use, 1-Use
-
Cooling discharge
temperature
3,4
15
8 ~ 18°C
1°C
Heating discharge
temperature
5,6
38
30~43°C
1°C
3
Fresh Duct discharge
temperature checking
Cooling discharge
temperature
1,2
18
15~25
1°C
Heating discharge
temperature
3,4
25
18~30
1°C
Содержание MWR-WE13