background image

ENGLISH-16

Using installation/service mode of ERV wired remote controller

Installation/service setting mode

•  If communication initialization is needed after the setting, the system resets automatically and 

communication is initialized .

Note

Main 

menu

Sub 

menu

Function

Factory 

setting

Page 

number

Range

Remarks

0

1

Reset

Reset to default value 

of ERV wired remote 

controller option setting

0

1

0-Disuse, 1-Reset

2

Reset to factory setting 

of ERV wired remote 

controller

0

1

0-Disuse, 1-Reset

3

Power Master Reset 3)*

0

1

0-Disuse, 1-Reset

4

Addressing Reset

0

1

0-Disuse, 1-Reset

1

1

Information 

on ERV 

wired 

remote 

controller

Checking the number of 

connected indoor units

0

1

0~16 EA

2

Checking the number of 

connected ERVs

0

1

0~16 EA

3

Checking the Micom 

code of ERV wired remote 

controller

none

3

Micom code

4

Checking the program 

version information 

of ERV wired remote 

controller

none

3

Modified date

2

1

Setting 

address/

option 2)*

Target

ERV View 

Master

3

Address of 

registerd devices / 

hexadecimal 5)*

2

Setting/checking main 

address

Main 

address of 

target

1

Main address 

(00H~4FH/

hexadecimal)

3

Setting/checking RMC 

address

RMC 

address of 

target

1

Group address 

(00H~FEH/

hexadecimal) 4*

4

Setting/checking product 

option

Basic option 

of target

10 1)*

Option code of 

indoor units or ERVs

5

Setting/Checking 

installation option 1

Installation 

option of 

target

10 1)*

Refer to the 

installation manual 

of connected 

indoor units or ERVs

6

Setting/Checking 

installation option 2

Installation(2) 

option of 

target

10 1)*

Refer to the 

installation manual 

of connected 

indoor units or ERVs

ERV Wired remote controller_MWR_VH12N_IM_EN_05309A-00.indd   16

2016-12-23   오후 6:02:55

Содержание MWR-VH12N

Страница 1: ...roller MWR VH12N ERV Energy Recovery Ventilator installation manual imagine the possibilities Thank you for purchasing this Samsung product ERV Wired remote controller_MWR_VH12N_IM_EN_05309A 00 indd 3 2016 12 23 오후 6 02 52 ...

Страница 2: ...stalling ERV wired remote controller 5 INSTALLATION Installing the ERV wired remote controller 6 Using installation service mode of ERV wired remote controller 15 Contents ERV Wired remote controller_MWR_VH12N_IM_EN_05309A 00 indd 2 2016 12 23 오후 6 02 53 ...

Страница 3: ...e or a contact center to disassemble or repair the product f f Potential risk of malfunction electric shock or fire The electric work must be done by qualified person according to national wiring regulations and installation guide f f If an unauthorized person performs the installation any resulting defects can cause malfunctions electrical shocks or fire accidents Install the product on a hard an...

Страница 4: ...hock or product damage Do not install the product in areas exposed to oil or vapor f f Potential risk of product damage or malfunction Do not put undue stress on the power cable f f Potential risk of broken cable and fire Do not install the product in areas with frequent use of acid or alkali spray f f Potential risk of electric shock or product malfunction Do not connect power cable to a communic...

Страница 5: ...lled by an installation expert Check and confirm the power is off before installing ERV wired remote controller Install the ERV wired remote controller cables in accordance with the electrical wiring rules and allow it to pass through the inner area of the wall so that other people can t reach it Caution External dimension Unit mm inch 122 0 4 80 75 0 2 95 16 6 0 65 ERV Wired remote controller_MWR...

Страница 6: ...mmunication wires correctly depending on the installation condition ū ū When the ERV wired remote controller is embedded on the wall Make the wire go through the hole in the center of the mounting plate ū ū When the ERV wired remote controller is installed on the wall Remove the thin parts on the front and mounting plate to make the wires go through as seen in the picture ū ū When the wire is exte...

Страница 7: ...remote controller by using two pieces of PVC wire remove the 30 cm of the sheath of the cable and install it only with the two pieces of wires Recommended specification AWG21 The followings are the specs of the compressed U terminal connectable to your ERV wired remote controller PCB W t G E F L Stud D Range of Permitted Wires Rated Size Stud Size Basic Size mm inch AWG mm2 inch2 mm2 inch2 mm inch...

Страница 8: ...llation press the Fan speed and buttons at the same time for more than five seconds ū ū The system is reset and tracking starts again 3 During the tracking the total number of currently searched products is displayed 4 It may take about 5 minutes at initial installation or when you re set the master setting If you want to perform system reset of ERV wired remote controller press the Fan speed and ...

Страница 9: ... of group address RMC address only the ERV connected to COM2 communication wire is individually controlled Caution When a upper controller is connected CN4 CN3 RED CN2 BLK ERV interface module MIM N10 ERV COM1 F1 F2 COM2 F3 F4 COM1 F1 F2 COM2 F3 F4 COM2 F3 F4 ERV wired remote controller ERV wired remote controller ERV wired remote controller ERV ERV Regardless of the setting of group address RMC a...

Страница 10: ...Vs connected to other ERV repeaters in a group CN4 CN3 RED CN2 BLK CN4 CN3 RED CN2 BLK ERV interface module MIM N10 ERV ERV ERV wired remote controller ERV interface module MIM N10 COM1 F1 F2 COM2 F3 F4 COM1 F1 F2 COM2 F3 F4 Regardless of the setting of group address RMC address only the ERVs connected to COM2 communication wire are controlled in a group You can control the maximum of 16 ERVs as a...

Страница 11: ...d remote controller Master COM2 F3 F4 ERV wired remote controller Slave For the setting of slave ERV wired remote controller please refer to the sections about the additional functions of the ERV wired remote controller Refer to the installation service mode 0 Master 1 Slave Caution ERV Wired remote controller_MWR_VH12N_IM_EN_05309A 00 indd 11 2016 12 23 오후 6 02 54 ...

Страница 12: ...changes When the number of ERVs indoor units or their address is changed Press the Fan speed and buttons at the same time for more than five seconds f f Your ERV wired remote controller is initialized and the device searches for the indoor units ERVs connected to your ERV wired remote controller again ERV Wired remote controller_MWR_VH12N_IM_EN_05309A 00 indd 12 2016 12 23 오후 6 02 54 ...

Страница 13: ...ecimal number Indoor unit Outdoor unit address Hexadecimal Number Indoor unit address Hexadecimal Number When an error occurs in ERVs or ERV repeaters Product Group Display b30 f f The product address for the error is displayed followed by the error code Example Error 101 occurs for ERV 10 decimal number ERV ERV repeater address Hexadecimal ERV address Hexadecimal When an error occurs in ERV wired...

Страница 14: ...led devices Error on installation of slave ERV wired remote controller When more than 2 slave ERV wired remote controllers are installed Communication error between master ERV wired remote controller and slave ERV wired remote controller Communication error between ERV wired remote controller and ERV indoor units After completing the tracking of ERV wired remote controller communication does not w...

Страница 15: ... menu number and press the Away button to enter the sub menu setting screen f f Using the buttons select a sub menu number and press the Away button to enter data setting screen f f When you enter the setting stage the current setting is displayed f f Refer to the chart for data settings f f Using the buttons select the settings and press the Away button to move to the next setting f f Press the S...

Страница 16: ...EA 3 Checking the Micom code of ERV wired remote controller none 3 Micom code 4 Checking the program version information of ERV wired remote controller none 3 Modified date 2 1 Setting address option 2 Target ERV View Master 3 Address of registerd devices hexadecimal 5 2 Setting checking main address Main address of target 1 Main address 00H 4FH hexadecimal 3 Setting checking RMC address RMC addre...

Страница 17: ...g optional functions of ERV wired remote controller ERV wired remote controller Master Slave 0 1 0 Master 1 Slave 2 Use of external interlock 0 1 0 Disuse 1 Use 5 1 Setting checking ERV Exhaust RPM none 2 0 9999 2 Intake RPM none 2 0 9999 3 Indoor temperature none 1 0 99 4 Outdoor temperature none 1 0 99 5 Indoor humidity none 1 0 99 6 Outdoor himidity none 1 0 99 7 CO2 sensor none 2 0 9999 8 Fan ...

Страница 18: ...displayed can be distinguished by operation mode On and Off icon SEG2 SEG6 SEG8 SEG12 ū ū On Heat EX By Pass Auto Quiet Away SEG14 SEG18 SEG20 24 ū ū Off Heat EX By Pass Auto Quiet Away SEG 2 3 PAGE 1 PAGE 6 PAGE 2 PAGE 7 PAGE 3 PAGE 8 PAGE 4 PAGE 9 PAGE 5 PAGE 10 SEG 14 15 SEG 4 5 SEG 16 17 SEG 6 8 SEG 18 20 SEG 9 10 SEG 21 22 SEG 11 12 SEG 23 24 Caution 2 When setting the address or option you c...

Страница 19: ...66 03 3 13 19 23 35 33 51 43 67 04 4 14 20 24 36 34 52 44 68 05 5 15 21 25 37 35 53 45 69 06 6 16 22 26 38 36 54 46 70 07 7 17 23 27 39 37 55 47 71 08 8 18 24 28 40 38 56 48 72 09 9 19 25 29 41 39 57 49 73 0A 10 1A 26 2A 42 3A 58 4A 74 0B 11 1B 27 2B 43 3B 59 4B 75 0C 12 1C 28 2C 44 3C 60 4C 76 0D 13 1D 29 2D 45 3D 61 4D 77 0E 14 1E 30 2E 46 3E 62 4E 78 0F 15 1F 31 2F 47 3F 63 4F 79 Note ERV Wired...

Страница 20: ...et on the sub menu f f Press the or button to select no 1 3 Press the Away button to enter the data setting stage f f When you enter the setting stage the current setting is displayed 4 Press the or button to select no 1 f f The status of external interlock changes from Disuse to Use 5 Press the Set button to complete the option settings f f Save the setting value and exit to sub menu 6 Press the ...

Страница 21: ...ENGLISH 21 02 INSTALLATION Memo ERV Wired remote controller_MWR_VH12N_IM_EN_05309A 00 indd 21 2016 12 23 오후 6 02 57 ...

Страница 22: ...ERV Wired remote controller_MWR_VH12N_IM_EN_05309A 00 indd 2 2016 12 23 오후 6 02 52 ...

Отзывы: