3
Set the lower/upper temperature limit.
You can set lower/upper temperature limit by selecting
'Enable'/'Disable'.
If desired temperature is lower than lower limit
temperature when the indoor unit is operating in cool
mode, DMS2 controls indoor unit to lower temperature
limit.
If desired temperature is higher than upper limit
temperature when the indoor unit is operating in heat
mode, DMS2 controls indoor unit to upper temperature
limit.
Lower temperature limit range: 18
℃(
65
°F)
~30
℃(
86
°F)
Upper temperature limit range: 16
℃(
61
°F)
~30
℃(
86
°F)
If the indoor unit is in Auto(Cool)/Auto(Heat) mode, lower/
upper temperature limit will be applied when the indoor
unit is operating in Auto mode.
However, if the upper temperature limit is set to
16°C(61°F)~17°C(64°F), the upper temperature limit in
Auto(Heat) mode is 18°C(65°F).
4
Click [Save].
Indoor unit usage restriction setting will be saved.